14 •
Technical Data
Technical Condition of the Devices
WAGO-I/O-SYSTEM
750
BACnet/IP Controller
2.2 Technical Data
Mechanic
Material
Polycarbonate, Polyamide 6.6
Dimensions W x H* x L
* from upper edge of DIN 35 rail
- Coupler/Controller (Standard)
- Coupler/Controller (ECO)
- Coupler/Controller (FireWire)
- I/O module, single
- I/O module, double
- I/O module, fourfold
- 51 mm x 65 mm x 100 mm
- 50 mm x 65 mm x 100 mm
- 62 mm x 65 mm x 100 mm
- 12 mm x 64 mm x 100 mm
- 24 mm x 64 mm x 100 mm
- 48 mm x 64 mm x 100 mm
Installation
on DIN 35 with interlock
Modular by
double feather key dovetail
Mounting position
any position
Marking
standard marking label type
group marking label 8 x 47 mm
Connection
Connection type
CAGE CLAMP®
Wire range
0.08 mm² ... 2.5 mm², AWG 28-14
Stripped length
8 … 9 mm,
9 … 10 mm for components with pluggable wiring
(753-xxx)
Contacts
Power jumpers contacts
blade/spring contact
self-cleaning
Current via power contacts
max
10 A
Voltage drop at I
max
< 1 V/64 modules
Data contacts
slide contact, hard gold plated
1.5 µm, self-cleaning
Climatic environmental conditions
Operating temperature
0 °C ... 55 °C,
-20 °C … +60 °C for components with extended
temperature range (750-xxx/025-xxx)
Storage temperature
-20 °C ... +85 °C
Relative humidity
5 % … 95 % without condensation
Resistance to harmful substances
acc. to IEC 60068-2-42 and IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75%
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for components are
taken, which are used in an environment involving:
– dust, caustic vapors or gases
– ionization radiation