Technical Data
•
17
Technical Condition of the Devices
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
For Products of the WAGO-I/O-SYSTEM 750 with ship specific approvals
supplementary guidelines are valid:
Electromagnetic compatibility
Immunity to interference acc. to Germanischer Lloyd (2003)
Test specification
Test values
Strength
class
Evaluation
criteria
IEC 61000-4-2 ESD
6 kV/8 kV (contact/air)
3/3
B
IEC 61000-4-3
electromagnetic fields
10 V/m 80 MHz ... 2 GHz
3
A
IEC 61000-4-4 burst
1 kV/2 kV (data/supply)
2/3
A
0.5 kV (line/line)
1
IEC 61000-4-5 surge
AC/DC
Supply:
1 kV (line/earth)
2
A
IEC 61000-4-6
RF disturbances
10 V/m 80 % AM
(0.15 ... 80 MHz)
3 A
Type test AF disturbances
(harmonic waves)
3 V, 2 W
-
A
Type test high voltage
755 V DC
1500 V AC
- -
Emission of interference acc. to Germanischer Lloyd (2003)
Test specification
Limit values
Frequency range
Distance
96 ... 50 dB (
μ
V)
10 kHz ... 150 kHz
60 ... 50 dB (
μ
V)
150 kHz ... 350 kHz
Type test
(EMC1, conducted)
allows for ship bridge control
applications
50 dB (
μ
V)
350 kHz ... 30 MHz
80 ... 52 dB (
μ
V/m) 150 kHz ... 300 kHz
3 m
52 ... 34 dB (
μ
V/m) 300 kHz ... 30 MHz
3 m
Type test
(EMC1, radiated)
allows for ship bridge control
applications
54 dB (
μ
V/m)
30 MHz ... 2 GHz
3 m
except: 24 dB (
μ
V/m)
156 MHz ... 165 MHz 3 m
Mechanical strength acc. to Germanischer Lloyd (2003)
Test specification
Frequency range
Limit value
2 Hz
≤
f < 25 Hz
± 1.6 mm amplitude (permanent)
25 Hz
≤
f < 100 Hz
4 g (permanent)
IEC 60068-2-6 vibration
(category A – D)
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes