BACnet/IP Controller 750-830
•
85
Fieldbus Node Start-up
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
The examples shown contain the following information:
Tab. 3-17: BootP Table Information
Information
Meaning
node1, node2
Any name for a node can be specified here.
ht=1
Here the hardware type of the network is specified.
For ETHERNET the hardware type is 1.
These numbers are explained in RFC1700.
ha=0030DE000100
ha=0030DE000200
Specify the hardware address (MAC ID) for the BACnet/IP controllers
here (hexadecimal).
ip= 10.1.254.100
ip= 10.1.254.200
Specify the IP address for the BACnet/IP controller here (decimal)
T3=0A.01.FE.01
Specify the gateway address here (hexadecimal)
sm=255.255.0.0
The subnet mask for the subnetwork to which the BACnet/IP controller
belongs can also be specified here (decimal).
The local network that is described in this description does not require a gate-
way. You can therefore apply the example "Example of entry with no gate-
way" here.
3. In the following text line, replace the 12-place hardware address located
behind “ha=“ in this example.
node1:ht=1:ha=0030DE000100:ip=10.1.254.100
4. In place of this, enter the MAC address for your own controller.
5. If you would like to specify a name for your fieldbus node, delete "node1"
in the text and enter the node name you wish to use.
node1:ht=1:ha=0030DE000100:ip=10.1.254.100
6. To assign the controller a specific IP address, mark the IP address given
here in the example after
“ip=“ and enter your own IP address.
node1:ht=1:ha=0030DE000100:ip=10.1.254.100
7. Since you do not need the second example
"Example of entry with gate-
way" here, place the number sign
(#) in front of the text line in Example
2 as a comment symbol:
# node2:hat=1:ha=003 0DE 0002 00:ip=10.1.254.200:
T3=0A.01.FE.01
This line will not be evaluated after this.