BACnet/IP Controller 750-830
•
121
Programming the PFC Using WAGO-I/O-PRO CAA
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
I/O config
Click the link "I/O config" to view the configuration and/or write access privi-
leges for the outputs of your fieldbus node.
The node structure created using the "WAGO-I/O-PRO CAA I/O Configura-
tor" hardware configuration tool is displayed in the window. If no modules are
shown in this window, no hardware configuration and, thus, no allocation of
write access privileges have been assigned. In this case, the handling defined
at the Web site "PLC" by the function "I/O configuration - Compatible han-
dling for ea-config.xml" will be applied to assign the write privileges for all
outputs either to the standard fieldbus, or to the PLC.
Fig. 3-20: Web-based Management System: I/O config
Additional Information
For more detailed information about the WAGO-I/O-
PRO
CAA I/O Configu-
rator, refer to the Section 3.1.7"Startup of Fieldbus Node."
When the function "I/O configuration – Insert monitoring entries into
ea-config.xml" is also activated at the Web site "PLC", the current process
values will also be shown for the data channels that are displayed.