WAGO-I/O-SYSTEM 750
Commissioning
59
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
Table 48: "Channel" parameters
Selection box
Possible settings
Important Note!
The setting has no impact on the process data
representation. The process value is always
saturated on the respective resistance limits of
the sensor type set.
(Principle: "Analog measuring instrument").
Underrange
At these points, the user can define limits, which will
result in setting the corresponding bits in the status byte
(see section "Control / status byte") in the event of an
underrange or overrange. The selected decimal value
always refers to the final output process value.
As delivered, the limits for the underrange/overrange
are selected, so that they cannot be exceeded. The
function is thereby virtually deactivated.
Range exceeded
At these points, the user can define limits, which will
result in setting the corresponding bits in the status byte
(see section "Control / status byte") in the event of an
underrange or overrange. The selected decimal value
always refers to the final output process value.
As delivered, the limits for the underrange/overrange
are selected, so that they cannot be exceeded. The
function is thereby virtually deactivated.
* Default setting