WAGO-I/O-SYSTEM 750
Commissioning
51
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
6.2.4.3
Reading/writing parameters (I/O module-specific)
Request (Application)
Table 43: Reading/writing parameters (Request)
Parameter
Value
Meaning
TGL_MS
!= TGL_SM
Initiate order
PRM_RW
= FALSE
Read access
= TRUE
Write access
MORE_PRM
= FALSE
The transmission of the parameter data is
terminated with the currently transmitted
parameter.
= TRUE
Further parameter data are to follow.
A0 ... A7
0 ... (n-1)
Address of parameter data
PRM0 ... PRM15 0 ... 65535
Parameter data for write access
Response (I/O module)
Table 44: Reading/writing parameters (Response)
Parameter
Value
Meaning
TGL_SM
== TGL_MS
Order executed
A0 ... A7
0 ... (n-1)
Address of parameter data mirrored
TIMEOUT
FALSE, TRUE Monitoring time expired
BUF_OFL
FALSE, TRUE Access outside the module parameter range
PRM_ERR
FALSE, TRUE Parameter/parameter set error
PRM0 ... PRM15 0 ... 65535
Parameter data for read access
Errors when exchanging parameter data are reported by the module in the error
flags TIMEOUT, BUF_OV and PRM_ERR.
When the last parameter has been transferred to the module (MORE_PRM =
FALSE), the entire parameter set is checked by the module and accepted if
correct. Otherwise, the module returns a parameterizing error (PRM_ERR =
TRUE).