![WAGO 750-464 Manual Download Page 28](http://html1.mh-extra.com/html/wago/750-464/750-464_manual_3197826028.webp)
28
Mounting
WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
Pos : 68 /All e Seri en (Allgemei ne Module)/Ü berschrif ten f ür alle Serien/Monti eren - D emontieren/M ontier en - Übersc hrift 1 @ 3\ mod_1225446744750_21. doc x @ 24900 @ 1 @ 1
4
Mounting
Pos : 69.1 /Serie 750 (WAGO-I/ O-SYST EM)/M ontieren/M ont agerei henf olge @ 3\ mod_1231770210031_21. doc x @ 25992 @ 2 @ 1
4.1
Mounting Sequence
All system components can be snapped directly on a carrier rail in accordance
with the European standard EN 50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual components are securely
seated on the rail after installation.
Starting with the coupler/controller, the I/O modules are mounted adjacent to each
other according to the project design. Errors in the design of the node in terms of
the potential groups (connection via the power contacts) are recognized, as the I/O
modules with power contacts (male contacts) cannot be linked to I/O modules
with fewer power contacts.
Pos : 69.2 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Vorsic ht/ Vorsicht: Verl etz ungsgefahr durc h s charf kantige M ess er kont akt e! @ 6\ mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged male contacts!
The male contacts are sharp-edged. Handle the module carefully to prevent injury.
Pos : 69.3 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Achtung/Achtung: Bus kl emmen in vorgegebener R eihenfolg e st ec ken! @ 6\ mod_1256194177073_21. doc x @ 43429 @ @ 1
Connect the I/O modules in the required order!
Never plug I/O modules from the direction of the end terminal. A ground wire
power contact, which is inserted into a terminal without contacts, e.g. a 4-channel
digital input module, has a decreased air and creepage distance to the neighboring
contact in the example DI4.
Pos : 69.4 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Achtung/Achtung: Aneinanderrei hen von Bus kl emmen nur bei of fener Nut! @ 6\ mod_1256193351448_21. doc x @ 43417 @ @ 1
Assemble the I/O modules in rows only if the grooves are open!
Please take into consideration that some I/O modules have no or only a few power
jumper contacts. The design of some modules does not allow them to be
physically assembled in rows, as the grooves for the male contacts are closed at
the top.
Pos : 69.5 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/Hinweis/Hi nweis: Busabsc hluss nicht vergess en! @ 6\ mod_1256194225557_21. doc x @ 43432 @ @ 1
Don't forget the end module!
Always plug an end module 750-600 onto the end of the fieldbus node! You must
always use an end module at all fieldbus nodes with the WAGO I/O System 750
fieldbus couplers/controllers to guarantee proper data transfer.
Pos : 69.6 /Dokumentation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0.doc x @ 21810 @ @ 1