WAGO-I/O-SYSTEM 750 

Connect Devices 

35 

750-464 2/4 AI RTD configurable 

 

 

Manual 

 

Version 1.0.1  

 

5.2.3 

750-464/020-000 (NTC) Version 

5.2.3.1 

4 x 2-Wire 

 

 

 

Important information for 4-channel operation 

Please note the special features in the following chapter 

 

Figure 16: Connection example, version 750-464/020-000 (NTC) 

5.2.3.2 

Special Features 

5.2.3.2.1  Influencing a Measuring Circuit Channel through a Quick Change in 

Temperature 

As a rule, temperatures change relatively slowly. If a channel's applied resistance 
changes over a short period of time by a large resistance value (large in relation to 
the converted temperature change), then this can influence the other channel 
within the measuring circuit. 

5.2.3.2.2  Underrange and Wire Break 

Depending on the hardware, it is not possible to distinguish between a 
(temperature) underrange and a wire break when using the NTC version 750-
464/020-000. In the case of wire break, an underrange is always detected. 

 

Pos : 77 /D okument ation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0. doc x @  21810  @   @  1 

 

 

 

Summary of Contents for 750-464

Page 1: ...docx 64941 1 Manual WAGO I O SYSTEM 750 2 4 AI RTD configurable 750 464 2 4 Channel Analog Input Module for RTDs Version 1 0 1 Pos 3 Alle Serien Allgemeine M odul e Hinweise zur Dokumentation Impressu...

Page 2: ...571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always ap...

Page 3: ...3 2 1 Data Contacts Internal Bus 17 3 2 2 Power Jumper Contacts Field Supply 18 3 2 3 CAGE CLAMP Connectors 19 3 2 4 Connections 4 Channel 2 Wire 19 3 2 5 Connections 2 Channel 3 Wire 19 3 2 6 Connect...

Page 4: ...ister 57 45 6 2 3 Parameter Sets 47 6 2 3 1 General Parameter Data System Parameter Range 47 6 2 3 2 I O Module Specific Parameter Data 47 6 2 4 Parameter transmission process 49 6 2 4 1 Determining t...

Page 5: ...Measurement 10 Ohm to 1 2 kOhm 92 7 4 10 Resistance Measurement 10 Ohm to 5 0 kOhm 93 7 4 11 Potentiometer 94 7 5 Data of the Version 750 464 020 000 NTC configurable 95 7 5 1 NTC 10 kOhm 95 7 5 2 NT...

Page 6: ...6 Table of Contents WAGO I O SYSTEM 750 750 464 2 4 AI RTD configurable Manual Version 1 0 1 List of Figures 115 List of Tables 116 Ende der Liste f r Textmar ke Verzeichnis_vor ne...

Page 7: ...en Variantenliste 750 464 Standar dversi on und Variante 020 000 4 AI NTC fr ei konfigurierbar 12 mod_1334642765393_21 docx 93584 1 Table 1 Variants Item Number Variant Designation 750 464 2 4 AI RTD...

Page 8: ...Serien Allgemei ne Module Wichtige Erl uterungen Sicherheits und sonstige Hinweise Vorsicht Vorsicht _War nung vor Personensch den allgemein_ Erl uterung 13 mod_1343310028762_21 docx 101038 1 Persona...

Page 9: ...RTD configurable Manual Version 1 0 1 Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 13 5 Dokumentation allgemei n Gl...

Page 10: ...Table 3 Font conventions Font type Indicates italic Names of paths and data files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greate...

Page 11: ...WAGO I O SYSTEM Wichtige Erl uterungen Personalqualifi kation 750 xxxx 3 mod_1224061208046_21 docx 24063 3 1 2 1 2 Personnel Qualifications All sequences implemented on Series 750 devices may only be...

Page 12: ...e berschrift 3 und Inhalt 3 mod_1221060446109_21 docx 21723 3 1 2 1 4 Technical Condition of Specified Devices The components to be supplied Ex Works are equipped with hardware and software configurat...

Page 13: ...Unfall verh tungsvorschriften beachten 6 mod_1260180657000_21 docx 46735 1 Pos 16 10 4 Alle Serien Allgemeine M odul e Wichtige Erl uter ungen Sicherheits und sonstige Hinweise Gefahr Gefahr Auf normg...

Page 14: ...ion lines Avoid reverse polarity of data and power supply lines as this may damage the devices involved Pos 16 11 6 Alle Serien Allgemeine M odul e Wichtige Erl uter ungen Sicherheits und sonstige Hin...

Page 15: ...ss Drahtbruch Bereichs ber unterschreitung 5 mod_1245391942765_21 docx 35672 1 A red fault LED per channel indicates a wire break a short circuit or that the signal is outside the measuring range Pos...

Page 16: ...40984217343_21 docx 31958 2 1 3 1 View Pos 21 Serie 750 WAGO I O SYSTEM Ger tebeschrei bung Ansicht Anal ogei ngangskl emmen Ansicht 750 0464 4 mod_1243405924578_21 docx 34005 1 Figure 1 View Table 4...

Page 17: ...pring contacts Figure 2 Data contacts Pos 25 2 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen Sicherheits und sonstig e Hinweise Achtung Achtung Buskl emmen nicht auf Goldfeder kontakte leg en 7 mod...

Page 18: ...tacts Table 5 Power jumper contacts Figure 3 Power jumper contacts Connection Type Number Function 1 Blade contact 2 Infeed of the field supply voltage UV and 0 V 2 Spring contact 2 Forwarding of the...

Page 19: ...l 2 wire Figure 4 Connections Connection Designation Channel Function 1 R1 1 Sensor 1 R 2 R1 1 Sensor 1 R 3 R3 3 Sensor 3 R 4 R3 3 Sensor 3 R 5 R2 2 Sensor 2 R 6 R2 2 Sensor 2 R 7 R4 4 Sensor 4 R 8 R4...

Page 20: ...ontacts 0 V Field supply 0 V Pos 32 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen Sicherheits und sonstig e Hinweise Hi nweis Hinweis Geschir mte Signalleitung en ver wenden 7 mod_1265723251019_21...

Page 21: ...missible measuring range broken wire short circuit D 2 Error R 2 off Normal operation red Overrange underrange of the admissible measuring range broken wire short circuit E 3 Status R 3 off Not ready...

Page 22: ...erating elements Pos 38 All e Seri en Allgemei ne Module berschriften f r alle Serien Ger tebeschreibung Schematisches Schaltbil d berschrift 2 4 mod_1240984441312_21 docx 31967 2 1 3 5 Schematic Diag...

Page 23: ...data Table 10 Technical data device Width 12 mm Height from upper edge of 35 DIN rail 64 mm Depth 100 mm Weight ca 48 g 3 6 2 Supply Table 11 Technical data supply Voltage supply Via system voltage t...

Page 24: ...Conversion time 320 ms Resolution 16 Bit Absolute accuracy at 25 C 0 2 of the full scale value typical 0 1 of the full scale value Temperature coefficient 20 ppm K typical 15 ppm K 3 6 5 Inputs NTC va...

Page 25: ...n T V ATEX T V 07 ATEX 554086 X I M 2 Ex d I M b II 3 G Ex nA IIC T4 Gc II 3 D Ex tc IIIC T135 C Dc 14 mod_1361949753233_0 docx 113015 1 T V 07 ATEX 554086 X I M2 Ex d I Mb II 3 G Ex nA IIC T4 Gc II 3...

Page 26: ...n Schiffszul assungen KR Kor ean R egister of Shi ppi ng 3 mod_1224492806109_0 docx 24232 1 KR Korean Register of Shipping Pos 57 All e Seri en Allgemei ne Module Zulassungen Schiffszul assungen LR Ll...

Page 27: ...it EN 61131 2 2007 6 mod_1259753054539_21 docx 46414 1 EMC CE Immunity to interference acc to EN 61131 2 2007 Pos 64 All e Seri en Allgemei ne Module N or men und Richtli nien EMV CE St r aussendung E...

Page 28: ...o prevent injury Pos 69 3 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen Sicherheits und sonstig e Hinweise Achtung Achtung Buskl emmen in vorgegebener R eihenfolg e stecken 6 mod_1256194177073_21 d...

Page 29: ...r en 6 mod_1256193963573_21 docx 43426 1 Perform work on devices only if the system is de energized Working on devices when the system is energized can damage the devices Therefore turn off the power...

Page 30: ...able Manual Version 1 0 1 Figure 11 Removing the I O module Electrical connections for data or power contacts are disconnected when removing the I O module Pos 70 D okumentation allgemei n Glieder ung...

Page 31: ...ne conductor at one single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals...

Page 32: ...ng on the signal cable Pos 76 Serie 750 WAGO I O SYSTEM Anschli e en Anschl ussbeispi ele Anal ogei ngangskl emmen Anschlussbeispi ele 750 0464 4 mod_1243491956171_21 docx 34054 344555344434455 1 5 2...

Page 33: ...wire break short circuit see section Register assignment Register 32 5 2 1 2 3 Influencing a Measuring Circuit Channel through a Quick Change in Temperature As a rule temperatures change relatively s...

Page 34: ...TD configurable Manual Version 1 0 1 5 2 2 2 2 x 3 Wire Figure 15 Connection example version 750 464 RTD 2 channel 2 x 3 Wire 5 2 2 3 1 x 2 Wire 1 x 3 Wire Due to the adjustability by channel all comb...

Page 35: ...s a rule temperatures change relatively slowly If a channel s applied resistance changes over a short period of time by a large resistance value large in relation to the converted temperature change t...

Page 36: ...gisters depends on the I O module used The bits 0 5 of the control byte contain the register number Via bit 6 R W the access direction read or write is set To switch on the register communication bit...

Page 37: ...se the same procedure as for channel 1 Set the parameters for channel 3 via control byte C2 status byte S2 and data bytes D4 and D5 Set the parameters for channel 4 via control byte C3 status byte S3...

Page 38: ...o s complement 1 Numeric values appear in amount sign format Bit 4 S5 FB250 output format 0 Numeric values appear in default format 1 Numeric values appear in S5 FB250 format Bit 5 Manufacturer or use...

Page 39: ...tput in Ohm 10R 5000R 15 Output in Ohm 10R 1200R Bit 12 15 Characteristic or sensor types of the 750 464 000 002 NTC version 0 NTC default 10 kOhm 1 NTC 20 kOhm 2 NTC Thermokon 10 kOhm 3 15 Reserved D...

Page 40: ...er before calculation of Y1 Bit 7 of the Feature register can be used to switch ON OFF mean value filtering Filtering is enabled immediately after determining the measured resistance value on the sens...

Page 41: ...ed 0 These bits are reserved and may not be changed Default settings Pos 82 Serie 750 WAGO I O SYSTEM In Betrieb nehmen Parametrier en ber Register kommuni kation C ontrol und Statusbyte bei R egister...

Page 42: ...ement Reg_Com 1 Register communication mirrored from control byte C1 Pos 84 Serie 750 WAGO I O SYSTEM In Betrieb nehmen Parametrier en ber Register kommuni kation C ontrol und Statusbyte bei R egister...

Page 43: ...t 3 Bit 2 Bit 1 Bit 0 Reg_Com R W Register number Register number Register number of the selected function cf Register Assignment section mirrored from control byte C3 R W 0 Read access acknowledgemen...

Page 44: ...terface SPS interface via the parameter exchange for the corresponding fieldbus systems e g PROFIBUS DP DP V1 via the asynchronous serial interface of the fieldbus coupler controller e g for WAGO I O...

Page 45: ...Table 34 Communication Control Parameters Parameter Value range Meaning A0 A7 0 255 Word address of the parameter to be read to be written TGL_MS FALSE TRUE Toggle bit to release new instructions fro...

Page 46: ...r read buffer were accessed PRM_ERR FALSE The parameter all parameters previously transmitted are valid TRUE At least one transmitted parameter was defective The flag can either be set after each para...

Page 47: ...arameters Address Mode Parameter Description 250 253 R W RESERVED Reserved for expansions 254 R W TIMEOUT This parameter contains the maximum permissible time in milliseconds that can elapse for the t...

Page 48: ...itching channel 3 0 2 wire operation for channel 3 is switched on 1 3 wire operation for channel 3 is switched on Bit 4 2 3 wire switching channel 4 0 2 wire operation for channel 4 is switched on 1 3...

Page 49: ...help of the toggle bit TGL_MS TGL_SM The communications control register R57 then polls the module until the latter acknowledges the execution of the order TGL_SM TGL_MS The possible orders to the pa...

Page 50: ...g factory settings Request Parameter Value Meaning TGL_MS TGL_SM Initiate order PRM_RW TRUE Write access A0 A7 255 Address of factory settings Response I O module Table 42 Restoring factory settings R...

Page 51: ...44 Reading writing parameters Response Parameter Value Meaning TGL_SM TGL_MS Order executed A0 A7 0 n 1 Address of parameter data mirrored TIMEOUT FALSE TRUE Monitoring time expired BUF_OFL FALSE TRU...

Page 52: ...ensoren 750 464 Parametrier dial og Allgemein 6 mod_1263886720210_21 docx 48043 3 1 6 3 1 2 4 Channel Input Module for Resistance Sensors 750 464 configuration dialog Figure 17 General dialog The para...

Page 53: ...n Exit Closes the configuration dialog Open Opens an existing parameterization file WAGO I O CHECK displays the default dialog for opening files Save Saves the current parameter in a parameter file WA...

Page 54: ...page with parameters for general settings Channel 1 Opens a page with parameters for channel 1 settings Channel 2 Opens a page with parameters for channel 2 settings Channel 3 Opens a page with param...

Page 55: ...sensoren 750 464 Allgemein 6 mod_1264071210328_21 docx 48261 4 1 6 3 3 1 2 4 Channel Analog Input Module for Resistance Sensors 750 464 general Figure 20 General parameters The following selection box...

Page 56: ...0 0464 2 4 Kanal Analog eingangsklemme f r Wi derstandssensoren 2 4 Kanal Analogei ngangsklemme f r Widerstandssensoren 750 464 Kan l e 6 mod_1263986474202_21 docx 48117 4 1 6 3 3 2 2 4 Channel Analog...

Page 57: ...er Off The Watchdog timer is not active The green LEDs illuminate continuously On The Watchdog timer is active If no process data is exchange with the bus coupler for 100 ms the green LEDs go out Mean...

Page 58: ...uit is not indicated in the status byte On A wire break or short circuit is indicated in the status byte The setting has no impact on the process data representation The process value is always satura...

Page 59: ...e selected decimal value always refers to the final output process value As delivered the limits for the underrange overrange are selected so that they cannot be exceeded The function is thereby virtu...

Page 60: ...e module can only be calibrated depending on the topology in 4 channel mode Figure 22 Calibration dialog To select the respective channel select the Channel 1 Channel 4 radio button To enter the value...

Page 61: ...ntly Use resistance decade boxes for calibration For best possible calibration of the module use resistors or resistance decade boxes that are a accurate as possible i e exhibit low tolerance Otherwis...

Page 62: ...nnel select the Channel 1 Channel 2 4 radio button To display the value in hexadecimal format select the hexadecimal radio button To display the value in decimal format select the decimal radio button...

Page 63: ...in the 2 wire offset field for a connected resistance temperature sensor the line resistance of the sensor has a direct impact on the measurement results and can this distort it The line resistance c...

Page 64: ...rozessabbild Kl emmenbus Analogei ngangsklemmen Pr ozessabbild 750 0464 5 mod_1245408102046_21 docx 35738 233223333333333323333333333323332333 1 7 1 Overview 7 1 1 Process Image for 2 Channel Operatio...

Page 65: ...lated temperature 1 The overrange limit is ON and the resistance value is below the lower temperature limit in relation to the calculated temperature 10R 1k2R 10R 5kR 0 The overrange limit see section...

Page 66: ...Register is taken into account Short Circuit Short Circuit 0 Indicate wire break short circuit see section Feature Register is OFF or there is no short circuit 1 Indicate wire break short circuit is...

Page 67: ...ature 1 The overrange limit is ON and the resistance value is below the lower temperature limit in relation to the calculated temperature 10R 1k2R 10R 5kR 0 The overrange limit see section Feature Reg...

Page 68: ...break short circuit see section Feature Register is OFF or there is no short circuit 1 Indicate wire break short circuit is ON and there is a short circuit Wire Break Wire Break 0 Indicate wire break...

Page 69: ...ature 1 The overrange limit is ON and the resistance value is below the lower temperature limit in relation to the calculated temperature 10R 1k2R 10R 5kR 0 The overrange limit see section Feature Reg...

Page 70: ...Register is taken into account Short Circuit Short Circuit 0 Indicate wire break short circuit see section Feature Register is OFF or there is no short circuit 1 Indicate wire break short circuit is...

Page 71: ...rrange limit is ON and the resistance value is below the lower temperature limit in relation to the calculated temperature 10R 1k2R 10R 5kR 0 The overrange limit see section Feature Register is OFF or...

Page 72: ...Register is taken into account Short Circuit Short Circuit 0 Indicate wire break short circuit see section Feature Register is OFF or there is no short circuit 1 Indicate wire break short circuit is...

Page 73: ...te hex LED error AI 1 2 Binary Hex Dec 9 00 1111 1000 0011 0000 0xF830 2000 0x51 on Short circuit 2 200 0 18 52 1111 1000 0011 0000 0xF830 2000 0x41 on Underrange 3 200 0 18 52 1111 1000 0011 0000 0xF...

Page 74: ...y Hex Dec 9 00 1111 1000 0011 0000 0xF830 2000 0x51 on Short circuit 2 200 0 37 04 1111 1000 0011 0000 0xF830 2000 0x41 on Underrange 3 200 0 37 04 1111 1000 0011 0000 0xF830 2000 0x00 off 100 0 120 5...

Page 75: ...ex Dec 9 00 1111 1000 0011 0000 0xF830 2000 0x51 on Short circuit 2 200 0 92 60 1111 1000 0011 0000 0xF830 2000 0x41 on Underrange 3 200 0 92 60 1111 1000 0011 0000 0xF830 2000 0x00 off 100 0 301 28 1...

Page 76: ...ex Dec 9 00 1111 1000 0011 0000 0xF830 2000 0x51 on Short circuit 2 200 0 185 20 1111 1000 0011 0000 0xF830 2000 0x41 on Underrange 3 200 0 185 20 1111 1000 0011 0000 0xF830 2000 0x00 off 100 0 602 56...

Page 77: ...1 2 Binary Hex Dec 9 00 1111 1101 1010 1000 0xFDA8 600 0x51 on Short circuit 2 60 0 69 52 1111 1101 1010 1000 0xFDA8 600 0x41 on Underrange 3 60 0 69 52 1111 1101 1010 1000 0xFDA8 600 0x00 off 50 0 74...

Page 78: ...00 1111 1100 1110 0000 0xFCE0 800 0x51 on Short circuit 2 80 0 66 60 1111 1100 1110 0000 0xFCE0 800 0x41 on Underrange 3 80 0 66 60 1111 1100 1110 0000 0xFCE0 800 0x00 off 50 0 86 16 1111 1110 0000 1...

Page 79: ...Binary Hex Dec 90 00 1111 1101 1010 1000 0xFDA8 600 0x51 on Short circuit 2 60 0 695 20 1111 1101 1010 1000 0xFDA8 600 0x41 on Underrange 3 60 0 695 20 1111 1101 1010 1000 0xFDA8 600 0x00 off 50 0 74...

Page 80: ...byte hex LED error AI 1 2 Binary Hex Dec 9 1111 1101 1010 1000 0xFDA8 600 0x51 on Short circuit 2 60 0 751 79 1111 1101 1010 1000 0xFDA8 600 0x41 on Underrange 3 60 0 751 79 1111 1101 1010 1000 0xFDA8...

Page 81: ...10 0000 0000 0110 0100 0x0064 100 0x41 on Underrange 3 10 0000 0000 0110 0100 0x0064 100 0x00 off 100 0000 0011 1110 1000 0x03E8 1000 0x00 off 200 0000 0111 1101 0000 0x07D0 2000 0x00 off 300 0000 101...

Page 82: ...10 0000 0000 0001 0100 0x0014 20 0x41 on Underrange 3 10 0000 0000 0001 0100 0x0014 20 0x00 off 100 0000 0000 1100 1000 0x00C8 200 0x00 off 200 0000 0001 1001 0000 0x0190 400 0x00 off 300 0000 0010 0...

Page 83: ...100 Table 69 Process image for 750 464 Potentiometer setting Percent Numeric value Status byte hex LED error AI 1 2 Binary Hex Dec 0 0 0000 0000 0000 0000 0x0000 0 0x00 off 20 0 0000 1111 1010 0000 0...

Page 84: ...2 1111 0011 1000 0 001 0xF381 3199 0x41 on Underrange 3 200 0 18 52 1111 0011 1000 0 000 0xF380 3200 0x00 off 100 0 60 256 1111 1001 1100 0 000 0xF9C0 1600 0x00 off 0 0 100 000 0000 0000 0000 0 000 0x...

Page 85: ...x41 on Underrange 3 200 0 37 04 1111 0011 1000 0 000 0xF380 3200 0x00 off 100 0 120 51 1111 1001 1100 0 000 0xF9C0 1600 0x00 off 0 0 200 00 0000 0000 0000 0 000 0x0000 0 0x00 off 100 0 277 01 0000 001...

Page 86: ...on Underrange 3 200 0 92 60 1111 0011 1000 0 000 0xF380 3200 0x00 off 100 0 301 28 1111 1001 1100 0 000 0xF9C0 1600 0x00 off 0 0 500 00 0000 0000 0000 0 000 0x0000 0 0x00 off 100 0 692 53 0000 0011 1...

Page 87: ...1 on Underrange 3 200 0 185 20 1111 0011 1000 0 000 0xF380 3200 0x00 off 100 0 602 56 1111 1001 1100 0 000 0xF9C0 1600 0x00 off 0 0 1000 00 0000 0000 0000 0 000 0x0000 0 0x00 off 100 0 1385 06 0000 00...

Page 88: ...41 959 0x41 on Underrange 3 60 0 69 52 1111 1100 0100 0 000 0xFC40 960 0x00 off 50 0 74 26 1111 1100 1110 0 000 0xFCE0 800 0x00 off 0 0 100 00 0000 0000 0000 0 000 0x0000 0 0x00 off 50 0 129 11 0000 0...

Page 89: ...Underrange 3 80 0 66 60 1111 1011 0000 0 000 0xFB00 1280 0x00 off 50 0 86 16 1111 1100 1110 0 100 0xFCE0 800 0x00 off 0 0 120 00 0000 0000 0000 0 000 0x0000 0 0x00 off 50 0 157 75 0000 0011 0010 0 000...

Page 90: ...959 0x41 on Underrange 3 60 0 695 20 1111 1100 0100 0 000 0xFC40 960 0x00 off 50 0 742 55 1111 1100 1110 0 000 0xFCE0 800 0x00 off 0 0 1000 00 0000 0000 0000 0 000 0x0000 0 0x00 off 50 0 1291 05 0000...

Page 91: ...00 0100 0 001 0x FC41 959 0x41 on Underrange 3 60 0 751 79 1111 1100 0100 0 000 0xFC40 960 0x00 off 50 0 790 88 1111 1100 1110 0 000 0xFCE0 800 0x00 off 0 0 1000 00 0000 0000 0000 0 000 0x0000 0 0x00...

Page 92: ...0 1010 0 001 0x00A1 161 0x41 on Underrange 3 10 0000 0000 1010 0 000 0x00A0 160 0x00 off 100 0000 0110 0100 0 000 0x0640 1600 0x00 off 200 0000 1100 1000 0 000 0x0C80 3200 0x00 off 300 0001 0010 1100...

Page 93: ...0 0001 0 100 0x0011 17 0x41 on Underrange 3 10 0000 0000 0001 0 100 0x0010 16 0x00 off 100 0000 0000 1100 1 000 0x00C8 200 0x00 off 200 0000 0001 1001 0 000 0x0190 400 0x00 off 300 0000 0010 0101 1 00...

Page 94: ...or the Potentiometer setting Detection of a wire break or short circuit is not possible depending on the model An overrange or underrange is also not possible depending on the sensor Accordingly the s...

Page 95: ...Process image for 750 464 020 000 NTC 10 kOhm setting Temperature C Resistance k Numeric value 1 Status byte hex LED error AI 1 2 Binary Hex Dec 50 0 1144 48 1110 1100 0111 1000 0xFE0C 500 0x41 on Un...

Page 96: ...C 20 kOhm setting Temperature C Resistance k Numeric value 1 Status byte hex LED error AI 1 2 Binary Hex Dec 50 0 2288 96 1110 1100 0111 1000 0xFE0C 500 0x41 on Underrange 3 50 0 2288 96 1110 1100 011...

Page 97: ...mokon setting Temperature C Resistance k Numeric value 1 Status byte hex LED error AI 1 2 Binary Hex Dec 40 0 426 50 1111 1110 0111 0000 0xFE70 400 0x41 on Underrange 3 40 0 426 50 1111 1110 0111 0000...

Page 98: ...us byte Hex LED error AI 1 2 Binary XF Hex Dec 50 0 1144 48 1111 1100 1110 0 001 0xFCE1 799 0x41 ein Underrange3 50 0 1144 48 1111 1100 1110 0 000 0xFCE0 800 0x00 aus 0 0 36 35 0000 0000 0000 0 000 0x...

Page 99: ...y XF Hex Dec 50 0 2288 96 1111 1100 1110 0 001 0xFCE1 799 0x41 on Underrange3 50 0 2288 96 1111 1100 1110 0 000 0xFCE0 800 0x00 off 0 0 70 20 0000 0000 0000 0 000 0x0000 0 0x00 off 25 0 20 00 0000 000...

Page 100: ...0x41 on Underrange3 40 0 426 48 1111 1101 1000 0 000 0xFD80 640 0x00 off 30 0 210 08 1111 1110 0010 0 000 0xFE20 480 0x00 off 0 0 34 28 0000 0000 0000 0 000 0x0000 0 0x00 off 25 0 10 00 0000 0001 100...

Page 101: ...Process value is saturated no change in statues byte error LED on Off On Process value is saturated error bit bit 0 Underrange or bit 1 Overrange Gen error bit 6 is set error LED on Process value is s...

Page 102: ...h Serie 750 3 mod_1234272230203_21 docx 27500 1 The WAGO I O SYSTEM 750 electrical equipment is designed for use in Zone 2 hazardous areas The following sections include both the general identificatio...

Page 103: ...Ex Bereichen Kennzeichnung f r Eur opa g em ATEX und IEC EX berschrift 3 3 mod_1224157620203_21 docx 24185 3 1 9 1 1 Marking for Europe according to ATEX and IEC Ex Pos 101 6 Serie 750 WAGO I O SYSTE...

Page 104: ...group Mining M2 Category High level of protection Ex Explosion protection mark d Mb Type of protection and equipment protection level EPL Flameproof enclosure I Explosion group for electrical equipmen...

Page 105: ...Ei nsatz i n Ex Bereichen Beispi elbedruckung der Ex i und IEC Ex i zugel assenen Buskl emmen gem CEN ELEC und IEC_2013 14 mod_1360569320118_21 docx 111298 1 Figure 26 Side marking example for approve...

Page 106: ...protection level EPL protection by enclosure ia Da Type of protection and equipment protection level EPL associated apparatus with intrinsic safety circuits for use in Zone 20 ib Db Type of protection...

Page 107: ...for a category 2 Zone 1 equipment Ex Explosion protection mark nA Gc Type of protection and equipment protection level EPL Non sparking equipment ia Ga Type of protection and equipment protection leve...

Page 108: ...kung gem N EC 500_2013 14 mod_1360580302684_21 docx 111353 1 Figure 28 Side marking example for I O modules according to NEC 500 Figure 29 Text detail Marking example for approved I O modules accordin...

Page 109: ...os 101 14 Alle Serien Allgemeine M odule Ei nsatz i n Ex Bereichen Errichtungsbesti mmungen Einl eitung _2013 14 mod_1360582328318_21 docx 111371 1 For the installation and operation of electrical equ...

Page 110: ...hes and potentiometers connected to the module may only be actuated when explosive atmosphere can be excluded 4 The connecting and disconnecting of the non intrinsically safe circuits is only permitte...

Page 111: ...ient protection according to EN 60079 0 and EN 60079 1 and the degree of protection IP64 The compliance of these requirements and the correct installation into an enclosure or a control cabinet of the...

Page 112: ...s and potentiometers connected to the module may only be actuated when explosive atmosphere can be excluded 4 The connecting and disconnecting of the non intrinsically safe circuits is only permitted...

Page 113: ...ient protection according to IEC 60079 0 and IEC 60079 1 and the degree of protection IP64 The compliance of these requirements and the correct installation into an enclosure or a control cabinet of t...

Page 114: ...s modules only The configuration interface Service connector is for temporary connection only Do not connect or disconnect unless the area is known to be non hazardous Connection or disconnection in a...

Page 115: ...onnection example version 750 464 RTD 2 channel 2 x 3 Wire 34 Figure 16 Connection example version 750 464 020 000 NTC 35 Figure 17 General dialog 52 Figure 18 Toolbar 53 Figure 19 Navigation 54 Figur...

Page 116: ...er 47 41 Table 24 Control Byte C0 for Register Communication 41 Table 25 Status Byte S0 for Register Communication 42 Table 26 Control Byte C1 for Register Communication 42 Table 27 Status Byte S1 for...

Page 117: ...image for 750 464 Pt200 setting acc IEC 751 85 Table 72 Process image for 750 464 Pt500 setting acc IEC 751 86 Table 73 Process image for 750 464 Pt1000 setting acc IEC 751 87 Table 74 Process image f...

Page 118: ...ite 9 mod_1285229376516_21 docx 64944 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Intern...

Reviews: