Commissioning
WAGO-I/O-SYSTEM 750
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
Table 48: "Channel" parameters
Selection box
Possible settings
SIEMENS Format
Off*
No display of status indicators
On
Display of status indicators in the bottom
three bits:
Bit 0: Overflow. Set for
Overrange/Underrange (if "Overflow
Limit" is active).
Bit 1: Error. Set for wire break/short
circuit (if "Indicate wire break/short
circuit" is active).
Bit 2: Always 0
Important Note!
If SIEMENS format is ON, the "Manufacturer
scaling" setting is not taken into account!
Indicate wire break/short
circuit
Off
A wire break or short circuit is not
indicated in the status byte.
On
A wire break or short circuit is indicated
in the status byte.
The setting has no impact on the process
data representation. The process value is
always saturated on the respective
resistance limits of the sensor type set.
Important Note!
The setting has no impact on the process data
representation. The process value is always
saturated on the respective resistance limits of
the sensor type set.
(Principle: "Analog measuring instrument").
Overflow Limit
Off
A measuring range overrange/underrange
is not indicated in the status byte.
On
A measuring range overrange/underrange
is indicated in the status byte.
The setting has no impact on the process
data representation. The process value is
always saturated on the respective
resistance limits of the sensor type set.