![WAGO 750-464 Manual Download Page 107](http://html1.mh-extra.com/html/wago/750-464/750-464_manual_3197826107.webp)
WAGO-I/O-SYSTEM 750
Use in Hazardous Environments 107
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
Table 88: Description of marking example for approved Ex i I/O modules according to ATEX and
IECEx
Gases
II
Equipment group: All except mining
3(1)G
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
3(2)G
Category 3 (Zone 2) equipment containing a safety
device for a category 2 (Zone 1) equipment
Ex
Explosion protection mark
nA Gc
Type of protection and equipment protection level
(EPL): Non-sparking equipment
[ia Ga]
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 0
[ia Gb]
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 1
IIC
Explosion group of gas and vapours
T4
Temperature class: Max. surface temperature 135°C