70
OPERATING MANUAL
VERSION 05/2017
ORDER NUMBER DOC 2357061
5 Only for Coriolis:
Density area
lower and upper value. The
actual density
must correspond to the
density display of the C-flow measuring transducer (with liquid in the system).
Correct the value here if necessary.
Temperature range
lower and upper value. The
actual temperature
must
correspond to the temperature display of the C-flow measuring transducer (with
liquid in the system). Correct the value here if necessary.
6 Like page 4, but for component B.
7 For component B:
AIS
(On/Off)
Mixing head valve with cycles
If a mixing head valve is fitted: "On" = Mixing head
valve cycles. "Off" = B valve cycles.
Mixing head valve flushing
"On" = A flushing valve is attached to the mixing head
valve.
Input type for mixing ratio
(A:B oder %B)
8 Like page 5, but for component B.
9–11 Like pages 6–8, but for component C.
12–14 Like pages 6–8, but for component D.
15
Alarm delay for air bubbles monitoring
How long can an air bubble be present
before the system stops ( alarms A114–A117).
Alarm delay no flow during filling
How long can filling be interrupted before an
alarm occurs (alarm A124). If set to 0.0 seconds, the function is deactivated.
Alarm delay no flow during flushing
How long can flushing be interrupted
before an alarm occurs (alarm A125)? When flushing, this alarm takes the place of
the pot life alarm. If the setting is "0.0 seconds", the function is deactivated, the pot
life continues and a pot life alarm occurs.
Alarm delay for Coriolis error
(alarms A128–A131).
Remote control
(On/Off)
Robot
(no/digital/bus): "Digital" = Robot is digitally connected. "Bus" = Robot is
connected via gateway.
Timeout for automatic logout
If the touch panel is not activated during the
defined time, then the password level is automatically reset to level 0. ("0 sec" = no
automatic logout.)