2021
5
100mm / 200mm Free Standing Woodburner Flue Kit
Installation Instructions
(see illustration page 4)
WARNING: THIS FLUE KIT HAS BEEN MANUFACTURED IN ACCORDANCE WITH
AS/NZS 2918:2001 AND TESTED TO APPENDIX F. TO ENSURE SAFETY THIS FLUE KIT
MUST BE INSTALLED AS OUTLINED IN THESE INSTRUCTIONS AND THE
APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR CODES.
WOOD FIRE AND FLUE CLEARANCES FROM COMBUSTIBLE WALLS MUST BE IN
ACCORDANCE WITH WOOD FIRE MANUFACTURER’S SPECIFICATIONS AND AS/NZS
2918:2001. THESE INSTALLATION INSTRUCTIONS ARE FOR TESTED APPLIANCES
ONLY
.
CAUTION: MIXING FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE
DIMENSIONAL SPECIFICATIONS OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS.
WHERE SUCH ACTION IS CONSIDERED, THE MANUFACTURER SHOULD BE CONSULTED IN THE
FIRST INSTANCE.
CAUTION: IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT THE INSTALLATION OF
THIS FLUE KIT COMPLIES WITH AS/NZS 2918:2001, THE APPLIANCE MANUFACTURERS
SPECIFICATIONS FOR FLUE PIPE SHIELD AND CEILING PLATE AND THAT THE RELEVANT BUILDING
CODES ARE ADHERED TO.
BENDS AND EXTENSIONS TO THE LENGTH OF A FLUE SYSTEM ARE PERMITTED (AS/NZS 2918:2001 4.1)
1. Locate Woodburner in its proposed position and mark a point on the ceiling that is directly above the
centre of the Woodburners Flue Spigot. Check that the Woodburners location allows the OUTER CASING
to clear all the structural roof timbers.
2. Cut a 200mm square hole in ceiling, directly above a cut hole in roof to accommodate OUTER CASING.
3. Fit timber nogs around ceiling i.e. Nogs form a 200mm square aperture that allows air to circulate freely
over the OUTER CASING surface.
4. Position the OUTER CASING so that it is flush with the underneath of the ceiling and protrudes through
the roof the required height. Note that AS/NZS 2918:2001 4.9.1(a) states, “the FLUE PIPE shall extend not
less than 4.6m above the top of the floor protector.” Refer to Diagram B. Fix into position using appropriate
fastenings.
a) If the FLUE PIPE is within 3 metres of the ridge, the FLUE PIPE must protrude at least 600mm above the
ridge of the roof.
b) If the distance from the ridge is more than 3 metres, the FLUE PIPE must protrude at least 1000mm above
roof penetration.
c) The FLUE PIPE must be more than 3 metres from any nearby structure. (Refer to diagram C).
Additional FLUE PIPE, OUTER CASING and/or INNER CASING may have to be added to ensure the
following.
•
The correct minimum roof penetration height.
•
Sufficient overall height to encase the FLUE PIPE which must extend a minimum of 4.6 metres from
the floor protector. Refer to diagram B.