![background image](http://html1.mh-extra.com/html/wagan/pure-line-3000/pure-line-3000_user-manual_3231203016.webp)
Pure Line 3000 by Wagan Tech
®
15
TROUBLESHOOTING
PROBLEM: Low or No Output Voltage – Fault LED Lit
Reason
Solution
Poor contact with battery, inverter
terminals
.
Clean terminals thoroughly. Reinstall
and tighten.
PROBLEM: Inverter Auto Shut Down – Fault LED Lit
Reason
Solution
Battery voltage is below 10.0 volts.
Charge or replace battery.
Inverter is too hot (thermal shut down
mode).
•
Allow inverter to cool.
•
Check for adequate ventilation.
•
Reduce the load on the inverter to
the specified TrueRated
™
power
max output.
PROBLEM: Inverter Shut Down – Fault LED Lit
Reason
Solution
Equipment being operated draws too
much power.
Do not use the equipment with this
inverter; use a higher wattage inverter.
PROBLEM: No AC Output – Yellow Ground Fault LED Lit
Reason
Solution
Ground fault is unintended AC current
that is flowing to ground. It can be
caused by faulty wiring, bad insulation,
very long wiring, and sparking
appliances.
Turn inverter OFF (O) to reset it, then
to ON (I). IF the inverter immediately
shuts off, disconnect each appliance
or wiring until the inverter will stay
on after reset. Examine the wiring or
appliance for unintended connections.
Repair or replace as necessary.