Connecting the inverter
SinePower
46
e
Caution – danger of electrocution!
If you wish to connect more than one user to the inverter and install
a socket distributor loop, you must arrange a circuit breaker (resid-
ual current circuit breaker) and set a grounding bridge in the
inverter, see chapter “Connect multiple appliances” on page 48.
z
When installed in vehicles or boats, the inverter must be connected to the
chassis or earth.
z
Before connecting, set the main switch (fig.
2
1, page 4) to “Off”.
z
When setting up a socket distribution circuit (mains set-up), you must
comply with VDE 0100.
z
Only use copper cables.
z
Keep the cables as short as possible. The cables cannot be longer than
1.8 m.
z
After running the cable, secure it with cable ties to the clips on the cable
socket.
z
Keep to the required cable cross section and fit a cable fuse as close to
the battery as possible on the positive cable (see table).
a
Warning!
If you do not fit a fuse to the
positive cable
, the cables can over-
load, which might result in a fire.
Device
Required cable cross section
Cable fuse
MSP 702
25 mm²
100 A
MSP 704
15 mm²
50 A
MSP 1012
35 mm²
200 A
MSP 1024
25 mm²
100 A
MSP 1512
35 mm²
200 A
MSP 1524
25 mm²
100 A
MSP 2012
70 mm²
250 A
MSP 2024
55 mm²
150 A
MSP 2512
95 mm²
400 A
MSP 2524
70 mm²
200 A