PAM-199-P
5.25
MIN (Overlap compensation)
5.26
MAX (output scaling)
5.27
TRIGGER (threshold value of MIN function)
Command
Parameters
Unit
Group
FUNCTION
MIN:I
X
MAX:I
X
TRIGGER
X
i= A|B
x= 0… 6000
x= 5000… 10000
x= 0… 3000
-
0.01 %
0.01 %
0.01 %
STD
196
The output signal is adapted to the valve by these commands. With the MAX value the output signal (the maxi-
mum valve current) will be defined. With the MIN value the overlap (dead band of the valve) will be compen-
sated. Via the TRIGGER command the activation point of the MIN function is set and so a non-sensitive range
around the zero-point
1
can be specified.
CAUTION
: If the MIN value is set too high, it influences the minimal velocity, which cannot be
adjusted any longer.
1
This dead band is necessary, in order to avoid unrequested activations caused by small variations of the input signal.
Eingang / Input
100%
10V
A
u
sg
a
n
g
/
O
u
tp
u
t
MAX
MIN
TRIGGER