Page 32 of 48
PAM-199-P
5.8
PIN:6 (Choice of the additional function of S1/PIN 6)
Command
Parameters
Unit
Group
FUNCTION
PIN:6
x
x= USCALE | RAMP
-
EXP
195
This parameter defines the functionality of digital input PIN:6
USCALE:
PIN 6 = active, USCALE will not scale the output.
PIN 6 = inactive, the output may be scaled by the USCALE parameter.
Ramps are active.
RAMP:
PIN 6 = active, the internal ramp generator is activated.
PIN 6 = inactive, the internal ramp generator is deactivated.
USCALE is inactive.
5.9
USCALE (Output current scaling depending on PIN:6)
Command
Parameters
Unit
Group
FUNCTION
USCALE
x
x= -10000… 10000 0.01 %
EXP
195
If the parameter PIN:6 is set to USCALE and the digital input S1 (PIN 6) is off, this parameter scales the out-
put current. The default setting is 10000 (100 %) which does not change the output.
If USCALE is set to -10000 the polarity of the output will be flipped by switching the digital input S1,
which allows for controlling the module with a unipolar analogue signal.
5.10 ENABLE_B (Switching of the ENABLE Function)
Command
Parameters
Unit
Group
FUNCTION
ENABLE_B x
x= ON|OFF
-
EXP
196
The setting of this parameter activates independent enable signals for channel A and B. If set to OFF, digital
input PIN 15 enables both output channels. If set to ON, digital input PIN 15 enables only channel A and digital
input PIN 6 enables channel B. If only one solenoid is to be controlled, ENABLE_B has to be set to ON and
only the corresponding digital input has to be switched on.