ELECTRICAL CONNECTIONS (SEE FIG. 2)
Electrical and grounding connections must comply with the national electrical code
and/or other local codes.
Disconnect the electrical power to the machine and follow lockout / tagout procedures.
The field connection box for field wire connection of Models VE30 and VE40 is located at the back of the
braising pan. A knockout hole is provided for a 1" (2.5 cm) conduit connection.
1. Remove the field connection box cover plate. Mount suitable 1" (2.5 cm) conduit fitting in the conduit
opening provided on the bottom surface.
2. Connect field wire to the terminal block as indicated on the wiring diagram. The wiring diagram is
located on the inside of the field box lid. Wire must be of the type suitable for 75°C service and at
the suitable gauge for loads shown on the data plate.
3. After making the connections, replace the control box cover plate.
4. The braising pan must be grounded by installing a properly grounded lead to the ground lug located
inside the field connection box.
ELECTRICAL DATA CHART
Model
Number
V (L-L)
Rated Line Current (A)
Rated
Power
(kW)
3Ø
1Ø
L1
L2
L3
VE30-FB
208
33.3
33.3
33.3
57.7
12
240
28.9
28.9
28.9
50.0
12
480
14.4
14.4
14.4
-
12
VE40-FB
208
45.9
41.6
45.9
76.9
16
240
39.7
36.1
39.7
66.7
16
480
19.9
18.0
19.9
-
16
These values are nominal ratings. Field wire connections must be capable of withstanding anticipated
surges.