CODE AND PROBLEM
PROBABLE CAUSE
SOLUTION
Er02 - RAM check sum error
Internal RAM malfunction
Cycle power.
Er03 - Ambient sensor error
Ambient temperature is below 32°F
Check ambient temperature at the
control.
Er04 - Configuration error
Microprocessor malfunction
Cycle power.
Ero5 - EEprom error
Power loss while storing data
Cycle power.
Er06 - Zone 1 A/D under flow error
•
Incorrect sensor type
•
Measuring temperature outside
the sensor range
•
Check the InP1 setup
parameter. Verify that it matches
the sensor.
•
Check sensor and connections
for a reversed or open sensor. If
the condition causing the error is
resolved, the error will clear.
Er07 - Zone 1 A/D overflow error
Open sensor
•
Check the InP1 setup
parameter. Verify that it matches
the sensor.
•
Check sensor and connections
for a reversed or open sensor. If
the condition causing the error is
resolved, the error will clear.
Er10 - Stack overflow error
Microprocessor malfunction
•
Cycle Power.
•
Check sensor and connections
for a reversed or open sensor.
Er11 - Open sensor error
Open sensor
•
Check the InP1 setup
parameter. Verify that it matches
the sensor.
•
Check sensor and connections
for a reversed or open sensor.
Er12 - Shorted sensor
•
Incorrect sensor type
•
Measuring temperature outside
the sensor range
•
Check the InP1 setup
parameter. Verify that it matches
the sensor.
•
Check sensor and connections
for a reversed or open sensor.
IGNITION MODULE DIAGNOSTICS
NUMBER OF LED FLASHES
INDICATES
POSSIBLE CAUSE
2 Flashes
Burner flame with no call for heat.
1.
Main gas valve stuck open,
burner on with no call for heat
from the temperature control
system. Replace main gas
valve.
2.
Check flame sensor and sensor
wire.
3.
Ignition module malfunction.
SG4 & SG6 Series Full Size Gas Convection Ovens - TROUBLESHOOTING
Page 55 of 56
F35626 Rev. B (1118)