PREVENT OF COMMON DANGERS AND RISKS
FILTER GRADE
FILTER GRADE
INITIAL PRESSURE
DIFFERENTIAL
RECOMMENDED MAXIMUM
PRESSURE DIFFERENTIAL
Panel Filter
G-2
(65% ≤ Am ≤ 80%)
25 Pa
150 Pa
G-3
(80% ≤ Am ≤ 90%)
40 Pa
150 Pa
G-4
(90% ≤ Am)
50 Pa
150 Pa
Bag Filter
G-4
(90% ≤ Am)
65 Pa
150 Pa
M-5
(40% ≤ Em ≤ 60%)
55 Pa
250 Pa
M-6
(60% ≤ Em ≤ 80%)
60 Pa
250 Pa
F-7
(80% ≤ Em ≤ 90%);
0.4 μm - 35%
115 Pa
250 Pa
F-8 F8
(90% ≤ Em ≤ 95%);
0.4 μm - 55%
165 Pa
350 Pa
After opening the service door, the filters can be taken out by pulling aside.
Synthetic bag filter can be cleaned by vacuumed or compressed air besides can be washed with the sensitive
detergent and warm water.
Humidifier should be cleaned regularly. The period changes according to the operating conditions, air
specifications and water quality. During periodic maintenance of humidifier, checks mentioned in its own manual
should be performed.
Sound attenuators can be taken out from the service door by unscrewing the components from the top and
bottom panels. Attenuators can be cleaned by vacuumed or compressed air.