32
the module is requested for the second time.
The setup of other linkage types in the system is identical to that of system linkage. The
difference is the input box for other information is added in the linkage condition setup. The
following section gives a brief description based on the illustration.
4.3.2 Building linkage setup
The drop-down selection box is incorporated into the building linkage. The corresponding
options will be displayed only after building information is registered.
Figure 4-38 Building linkage setup
4.3.3 Floor integration setup
The floor-related linkage conditions in the system include two types: type output and point
input.
The figure below presents the floor integration setup of type output, floor options are
unavailable in the condition setup, a check box "scroll" is added only and a certain or some
equipment types can be selected in the optional module list.
The floor integration linkage of type output means: when detector or module of any
specified type at any floor gives an alarm, the equipment of a certain type or some types at the
floor will carry out actions completely. If "scroll" is selected, the equipment of same type at
adjacent floors will carry out actions in the meantime.
Figure 4-39 Floor integration - type output
The linkage relation can be used cooperatively with the function "equipment type add",
which can greatly reduce setup workload of the user.
The linkage relation of floor type output shall be immediately started
and cannot be set at delay time!