background image

2b

  Place Batteries in Box with 

 

Terminals to the Left  

2c

  Attach Wires from Battery Board

 

Red wires = (+)                                            

          Black wires = (-)                  

2d

  Verify That Battery LED is On

 

If LED is not on, cycle AC power off and then  

 back 

on.

INSTALL AND CONNECT BATTERIES

Note: 

Allow 24 hours for batteries to fully charge

2a

  Turn On AC Breaker to 

 

Energize Power Supply  

Batter

y 1              Batter

y 2

Black Wires = (-)

+

+

BB LED
(Amber)

On-Solid

AC On

Batteries

Charging

On-Blinking

AC Off

Batteries 

Supplying 

Power

Battery Supervision Terminals
(Form C Dry Contacts)

Active

AC On

Inactive

AC Off

(Shown 

AC Off) 

NO
C
NC

Red Wires = (+)

NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR 
KEYLOCK

Incorrect connection may cause damage to the batteries

WARNING:

!

Summary of Contents for PS914

Page 1: ... Load For protection against risk of fire replace fuse with same type and rating CAUTION INST INSTRUCTIONS 44487056 INST INSTRUCTIONS 44487098 INST INSTRUCTIONS 44487106 INST INSTRUCTIONS 44487080 INST INSTRUCTIONS 44487106 INST INSTRUCTIONS 44487106 INST INSTRUCTIONS 44487072 INST INSTRUCTIONS 44487064 Inputs I1 I2 Dry contacts required Closed Active Connect control contacts between SC Signal Com...

Page 2: ...icable codes Install the PS914 indoors within the protected premises Check national and local codes for additional installation requirements Enclosure must be firmly mounted to a solid surface using hardware suitable for the surface x x 2 SECURE ENCLOSURE DOOR If No Keylock Enclosure will be secured with 2 screws as shown done as last step If Keylock Remove knockout and insert key cylinder then sl...

Page 3: ...ure AC Breaker is Turned Off OR 12 VDC Output Setting 24 VDC Output Setting Minimum of 1 4 separation between AC and DC wiring as well as power limited and non power limited Note 4 INSTALL 900 BB BATTERY BACKUP IF INCLUDED 4a Place Batteries in Box with Terminals to the Left 4b Attach Wires from Battery Board Red wires Black wires Note Allow 24 hours for batteries to fully charge Battery 1 Battery...

Page 4: ...ct Use Jumper to Select Function OR Sequential Individual 6b Plug 2RS Cable into any Available Option Connector 6c Secure Board with Screws Option 2 Option 1 1 2 If installing board in location 2 rotate board 180 Note 24VDC output setting required when EL device connected DANGER Ensure AC breaker is turned off when installing or wiring option boards NOTE WHEN INSTALLATION IS COMPLETE SECURE ENCLOS...

Page 5: ...e Range 32 120 F 0 49 C Compliance UL 294 ULC S318 RoHS FCC Part 15 Fire Alarm Input Accepts 900 FA Fire Alarm Board Optional 2010 Ingersoll Rand Company 1 877 671 7011 44487080 Rev 10 10_a 1 INSTALL 4RL BOARD S INTO POWER SUPPLY 1a Review Available 900 4RL Mounting Locations Gray PS902 PS904 PS914 PS906 1 1 2 2 3 1 1b Plug 4RL Cable into any Available Option Connector 1c Secure Board s with Screw...

Page 6: ...mes every 5 seconds Security Interlock Function SI Controls multi door interlocks Two through six door systems are possible additional boards required for three to six doors Function LED will blink three times every 5 seconds For 4TD Go to pages 3 4 For AO Go to pages 5 6 For SI Go to pages 7 8 Basic Troubleshooting Go to page 8 Powered Outputs Default Dry Contact Outputs Optional OPTIONAL DRY CON...

Page 7: ...dds 10 seconds to the time delay when ON 7 Adds 20 seconds to the time delay when ON 8 Adds 40 seconds to the time delay when ON DIP switches on SW1 can be turned ON by moving them in the direction that the arrow is pointing Switches below shown in OFF position Summary of Operation Output turns ON when input is activated closed Time delay begins when input is released opened Locking Device output ...

Page 8: ... Control 1 jumper I1 I2 To control EL1 EL4 with Access Control 1 jumper I1 I2 I3 I4 0 100 ft use 14 gauge stranded wire 0 200 ft use 12 gauge stranded wire Note Fail secure output only allowed if approved by Authority Having Jurisdiction GND NC2 C2 NO2 I2 NC1 C1 NO1 I1 SC GND NC4 C4 NO4 I4 NC3 C3 NO3 I3 SC 4RL 120 240 VAC 50 60Hz Access Control 2 Mag Lock 2 Mag Lock 1 Access Control 1 PS902 or PS9...

Page 9: ...ll trigger one locking device Sequential Mode One input will trigger two locking devices 4 Turn OFF default to enable Individual Mode single doors Turn ON to enable Sequential Mode double doors Set Time Delay 0 30 seconds 2 second increments 0 Sec Switches 5 8 OFF 30 Sec Switches 5 8 ON 5 Adds 2 seconds to the time delay when ON 6 Adds 4 seconds to the time delay when ON 7 Adds 8 seconds to the ti...

Page 10: ...itch 1 on SW1 AO WIRING EXAMPLE DOUBLE DOORS Summary of Operation Access control input unlocks both doors Both latch monitors LX trigger auto operators Double Door Board Configuration 1 Position jumpers for dry contact for outputs 2 and 4 see page 2 2 Turn on switches 4 5 and 6 on SW1 6 second time delay 3 If LX is not used turn on switch 1 on SW1 SW1 SW2 1 2 3 4 5 6 7 8 ON OFF 1 2 SW1 1 2 3 4 5 6...

Page 11: ...me delay when ON SI INPUT OUTPUT TERMINAL BLOCK DEFINITIONS Input 1 Access Control 1 Input 2 Access Control 2 Input 3 Lock Monitor 1 Input 4 Lock Monitor 2 Output 1 Lock 1 Output 2 Lock 2 Output 3 Follows Output 1 by 5 Sec Output 4 Follows Output 2 by 5 Sec See page 2 for dry contacts GLOBAL INTERLOCK SWITCH SETTING EXAMPLES SI Board 1 SI Board 2 SI Board 3 Application SW1 3 SW1 4 SW1 3 SW1 4 SW1 ...

Page 12: ...PS 900 main board F1 fuse Use voltmeter to verify 12 VDC or 24 VDC output on PS 900 main board 900 4RL Function LED yellow is blinking but inputs and outputs are inactive If 900 FA option is installed onto 900 4RL verify fire alarm contacts are closed across FA1 and FA2 If 900 FA option is not installed then verify jumper wire is installed into FA JMPR connector on the 4RL board Inputs and outputs...

Page 13: ... DAN GER WAR NING WAR NING Remove Jumper from Option Board Install 900 FA to Option Board Choose Option Board where 900 FA is to be Installed 1 2 3 Option board may be in any of these three locations Note If using battery backup location 3 is not available To avoid risk of electric shock turn off AC power to power supply before installing or wiring 900 FA board In the event a fire alarm is active ...

Page 14: ... Reset Temporarily close to reset Fire Alarm Contact Closed no fire Open fire Fire Alarm Contact Closed no fire Open fire Fire Alarm Contact Closed no fire Open fire Note Use 18 gauge wire for all wiring Wire length dependent on physical layout Remove Jumper Install 900 FA Here Note Complete power failure shall result in a fail safe operation When connected to a fire alarm releasing control unit t...

Page 15: ... 24V Battery Type 12VDC 7Ah Gel Sealed Rechargeable Battery 2 included 5 Year Service Life Replacement Part Number Schlage 991280 To avoid risk of electric shock turn off AC power to power supply before installing or wiring 900 BB board DANGER Charge only Schlage 991280 batteries Other types may burst causing personal injury and damage Observe the proper polarity when connecting the batteries CAUT...

Page 16: ...r batteries to fully charge 2a Turn On AC Breaker to Energize Power Supply Battery 1 Battery 2 Black Wires BB LED Amber On Solid AC On Batteries Charging On Blinking AC Off Batteries Supplying Power Battery Supervision Terminals Form C Dry Contacts Active AC On Inactive AC Off Shown AC Off NO C NC Red Wires NOTE WHEN INSTALLATION IS COMPLETE SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK Incorrect c...

Page 17: ... DAN GER WAR NING WAR NING Remove Jumper from Option Board Install 900 FA to Option Board Choose Option Board where 900 FA is to be Installed 1 2 3 Option board may be in any of these three locations Note If using battery backup location 3 is not available To avoid risk of electric shock turn off AC power to power supply before installing or wiring 900 FA board In the event a fire alarm is active ...

Page 18: ... Reset Temporarily close to reset Fire Alarm Contact Closed no fire Open fire Fire Alarm Contact Closed no fire Open fire Fire Alarm Contact Closed no fire Open fire Note Use 18 gauge wire for all wiring Wire length dependent on physical layout Remove Jumper Install 900 FA Here Note Complete power failure shall result in a fail safe operation When connected to a fire alarm releasing control unit t...

Page 19: ... 24V Battery Type 12VDC 7Ah Gel Sealed Rechargeable Battery 2 included 5 Year Service Life Replacement Part Number Schlage 991280 To avoid risk of electric shock turn off AC power to power supply before installing or wiring 900 BB board DANGER Charge only Schlage 991280 batteries Other types may burst causing personal injury and damage Observe the proper polarity when connecting the batteries CAUT...

Page 20: ...r batteries to fully charge 2a Turn On AC Breaker to Energize Power Supply Battery 1 Battery 2 Black Wires BB LED Amber On Solid AC On Batteries Charging On Blinking AC Off Batteries Supplying Power Battery Supervision Terminals Form C Dry Contacts Active AC On Inactive AC Off Shown AC Off NO C NC Red Wires NOTE WHEN INSTALLATION IS COMPLETE SECURE ENCLOSURE DOOR WITH SCREWS OR KEYLOCK Incorrect c...

Reviews: