Buzzer  sounds  3  times 
and  Red  LED  blinks  3 
times 

every 

eight 

seconds

 

Voltage at the DC input 

terminals reads below; 

10.2±0.2VDC(12V version) 

20.4±0.4VDC(24V version) 

40.8±0.8VDC(48V version) 

1.Check that the battery is fully 

charged. Recharge, if low 

2. Check that the battery cables 

are  thick  enough  to  carry  the 

required 

current 

over 

the 

required  length.  Use  thicker 

cables, if required 

3.  Tighten  connections  of  the 

battery input circuit.                                         

 

 

Buzzer  sounds  4  times 
and  Red  LED  blinks  4 
times 

every 

eight 

seconds

 

Higher    input DC voltage than 

15.5±0.2VDC(12V version), 

31±0.4VDC(24V version), 

62±0.8VDC(48V version)

 

1.  Check  that  the  voltage at  the 

DC input terminals is more than 

15V/30V/60V DC. 

2.  Ensure  that  the  maximum 

charging  voltage  of  the  battery 

charger 

/alternator 

solar 

charge  controller  is  below  15 

V/30V/60VDC 

3.  Ensure  that  an  un-regulated 

solar panel or wind turbine is not 

used to charge a battery 

 

 

 

 

 

 

 

Buzzer  sounds  5  times 
and  Red  LED  blinks  5 
times 

every 

eight 

seconds

 

System overheating

 

1. Check that the fan is working. 

If not, the fan / fan control circuit 

may be defective

 Call Technical 

Support

 

2.  If  the  fan  is  working,  check 

that  the  ventilation  slots  on  the 

suction  side  and  the  openings 

on the discharge side of the fan 

are not obstructed 

3. If the fan is working and the 

openings  are  not  obstructed, 

check 

that 

enough 

cool 

replacement  air  is  available. 

Also  check  that  the  ambient  air 

temperature is less than 45º C 

4. Reduce the load to reduce the 

heating effect 

5. After the cause of overheating 

is  removed  and  the  unit  cools 

down, it will reset automatically 

 

Red LED

 constantly flashing

 

The  loads  is  200%  higher    than 

rated power. 

1. Disconnect the load 

2. Reduce the load   

3.Cool the unit.

 

 

Summary of Contents for KS2000P

Page 1: ...put 5V 500mA Optional Variable speed DC fans Controlled by Temperature and Load Protection LED Indicator Audible Alarm 12V or 24V Models Input voltage range 15 25 Output voltage regulation 10 Output w...

Page 2: ...y Bank 7 3 3 Battery wiring examples 7 8 3 4 Placement of the inverter 8 3 5 Mounting position of the inverter 9 3 6 Connections 9 4 Important Safety Instructions 9 10 5 Protection Feature 10 6 Troubl...

Page 3: ...e sine wave inverter With pure sine wave motors start easier and run cooler As well some equipment may only operate properly with a pure sine wave inverter such as laser printers variable speed motors...

Page 4: ...F switch via a communication cable H Hardwire Terminal Block 2500W to 6000W Note When the load current is 10A 2300W You must use the output terminal connection which can be found inside the AC output...

Page 5: ...e is more than 45 the fan s rotational speed is 100 B DC Battery Terminals Connect the inverter to battery or other power sources Negative and Positive DC terminals should be kept insulated to protect...

Page 6: ...or printed on most appliances and equipment In some cases a tool will be rated in amperes To convert from amps to watts multiply Amps x AC voltage Watts Eg 2 0 A x 230 V 460 Watts This formula yields...

Page 7: ...st be capable of delivering to the inverter divide the load watts by ten For example a 500 watt appliance load will need 50 amps at 12 volts DC Using the 500 watts or 50 amps for 10 hours example as a...

Page 8: ...clearance around the unit for air flow Do not place items on or over the inverter during operation Make sure that air is allowed to circulate freely around the unit A fan is helpful in the case where...

Page 9: ...tions 1 Do not attempt to connect the output to any other power source including any AC mains 2 Make sure the opening to the ventilation fan and vent holes are not blocked 3 Avoid pulling on the cords...

Page 10: ...cally shut off Input Over Voltage Protection When input voltage reach 15 5V 0 2V for 12V input inverter 31V 0 4V for 24V input inverter 62V 0 8V for 48V input inverter The Buzzer will sound 4 times an...

Page 11: ...ntact Replace if blown 3 Check that all connections in the battery input circuit are tight Polarity of the input voltage has been reversed that has blown the DC side fuses Note Reverse polarity may ca...

Page 12: ...harger alternator solar charge controller is below 15 V 30V 60VDC 3 Ensure that an un regulated solar panel or wind turbine is not used to charge a battery Buzzer sounds 5 times and Red LED blinks 5 t...

Page 13: ...Open sealed lead acid battery Dimension L W H cm 17 15 5 5 21 15 7 21 15 7 37 5 15 7 2 36 22 9 29 22 9 Packing PCS CTN 12 6 6 4 2 2 KGS CTN 16 5 14 5 15 5 14 5 11 5 13 5 MEAS L W H cm 44 42 32 42 34 4...

Page 14: ...dically with a dry cloth to prevent accumulation of dust and dirt At the same time tighten the screws on the DC input terminals 9 WARRANTY We guarantee this product against defects in materials and wo...

Page 15: ...lash load power is less than 5 of rated power or standby AC ON Solid green Inverter s output is continuous Fault Turns red to show fault refer to Troubleshooting of Inverter Manual Connecting the Comm...

Page 16: ...0 Ah 24V 6mm 1 Red 1 Black 20A 4 80Ah 48V 4mm 1 Red 1 Black 10A 4 40Ah 1500W 12V 10mm 2 Red 2 Black 35A 6 250Ah 24V 6mm 2 Red 2 Black 20A 6 125Ah 48V 4mm 2 Red 2 Black 10A 6 60Ah 2000W 12V 16mm 2 Red...

Reviews: