background image

 

6

 

 

C.

 

Fuse

 

Fuses for DC Input have been fitted to the rear panel. So as to be easily accessible in 
order to facilitate checking & replacing if required. Depending on the installation this 
maybe possible without removing the inverter.   
 

3. HOW TO USE INVERTER   

3.1 Load consideration 

When an appliance with a motor starts, it requires a momentary surge of power. This 
surge  of  power  is  the  “starting  load”  or  “peak  load”.  Once  started,  the  appliance 
requires less power to continue to operate. This is known as the “continuous load”. It 
is important to know the starting loads and the continuous loads of the appliances that 
are to be powered by the inverter.   
Appliance power is rated in watts. This information is usually stamped or printed on 
most  appliances  and  equipment.  In  some  cases,  a  tool  will  be  rated  in  amperes.  To 
convert from amps to watts, multiply:   
Amps x AC voltage = Watts          (Eg: 2.0 A x 230 V = 460 Watts) 
This  formula  yields  an  approximation  of  the  continuous  wattage  load  of  that 
appliance.   
The startup load of an appliance is a major factor of whether this inverter can power 
it.   
Startup  load  is  momentary.  With  many  appliances,  it  is  approximately  twice  the 
continuous  load,  but  some  appliance  startup  loads  can  be  as  high  as  eight  times  the 
continuous load.   
If you are unsure of your equipments Power requirements an ‘Energy use’ meter may 
be used to measure the 

starting peak

 & 

continuous wattage

 . 

 
In order to lesson the possibility of damaging the inverter or the equipment. 
This inverter will automatically shut down in the event of an output overload, 
When this occurs a Red LED indicator will turn on and the Buzzer signals a fault. 
 
 

 

Summary of Contents for KS2000P

Page 1: ...put 5V 500mA Optional Variable speed DC fans Controlled by Temperature and Load Protection LED Indicator Audible Alarm 12V or 24V Models Input voltage range 15 25 Output voltage regulation 10 Output w...

Page 2: ...y Bank 7 3 3 Battery wiring examples 7 8 3 4 Placement of the inverter 8 3 5 Mounting position of the inverter 9 3 6 Connections 9 4 Important Safety Instructions 9 10 5 Protection Feature 10 6 Troubl...

Page 3: ...e sine wave inverter With pure sine wave motors start easier and run cooler As well some equipment may only operate properly with a pure sine wave inverter such as laser printers variable speed motors...

Page 4: ...F switch via a communication cable H Hardwire Terminal Block 2500W to 6000W Note When the load current is 10A 2300W You must use the output terminal connection which can be found inside the AC output...

Page 5: ...e is more than 45 the fan s rotational speed is 100 B DC Battery Terminals Connect the inverter to battery or other power sources Negative and Positive DC terminals should be kept insulated to protect...

Page 6: ...or printed on most appliances and equipment In some cases a tool will be rated in amperes To convert from amps to watts multiply Amps x AC voltage Watts Eg 2 0 A x 230 V 460 Watts This formula yields...

Page 7: ...st be capable of delivering to the inverter divide the load watts by ten For example a 500 watt appliance load will need 50 amps at 12 volts DC Using the 500 watts or 50 amps for 10 hours example as a...

Page 8: ...clearance around the unit for air flow Do not place items on or over the inverter during operation Make sure that air is allowed to circulate freely around the unit A fan is helpful in the case where...

Page 9: ...tions 1 Do not attempt to connect the output to any other power source including any AC mains 2 Make sure the opening to the ventilation fan and vent holes are not blocked 3 Avoid pulling on the cords...

Page 10: ...cally shut off Input Over Voltage Protection When input voltage reach 15 5V 0 2V for 12V input inverter 31V 0 4V for 24V input inverter 62V 0 8V for 48V input inverter The Buzzer will sound 4 times an...

Page 11: ...ntact Replace if blown 3 Check that all connections in the battery input circuit are tight Polarity of the input voltage has been reversed that has blown the DC side fuses Note Reverse polarity may ca...

Page 12: ...harger alternator solar charge controller is below 15 V 30V 60VDC 3 Ensure that an un regulated solar panel or wind turbine is not used to charge a battery Buzzer sounds 5 times and Red LED blinks 5 t...

Page 13: ...Open sealed lead acid battery Dimension L W H cm 17 15 5 5 21 15 7 21 15 7 37 5 15 7 2 36 22 9 29 22 9 Packing PCS CTN 12 6 6 4 2 2 KGS CTN 16 5 14 5 15 5 14 5 11 5 13 5 MEAS L W H cm 44 42 32 42 34 4...

Page 14: ...dically with a dry cloth to prevent accumulation of dust and dirt At the same time tighten the screws on the DC input terminals 9 WARRANTY We guarantee this product against defects in materials and wo...

Page 15: ...lash load power is less than 5 of rated power or standby AC ON Solid green Inverter s output is continuous Fault Turns red to show fault refer to Troubleshooting of Inverter Manual Connecting the Comm...

Page 16: ...0 Ah 24V 6mm 1 Red 1 Black 20A 4 80Ah 48V 4mm 1 Red 1 Black 10A 4 40Ah 1500W 12V 10mm 2 Red 2 Black 35A 6 250Ah 24V 6mm 2 Red 2 Black 20A 6 125Ah 48V 4mm 2 Red 2 Black 10A 6 60Ah 2000W 12V 16mm 2 Red...

Reviews: