background image

13

Mynute 24m

A 130mm hole is required for the passage of the
concentric terminal through the ceiling and/or roof.

Depending on site conditions it may be preferable
to install the terminal assembly prior to fitting the
twin flue pipes. Fit the appropriate flashing plate to
the roof and insert the vertical flue terminal through
the flashing plate from the outside, ensuring that
the collar on the flue terminal fits over the flashing.
Push-fit the twin flue pipes onto the concentric to
twin converter ensuring that the exhaust pipe
connects to the exhaust connection on the con-
centric to twin converter. If necessary cut the plain
ends (male) of the twin flue pipes to allow connec-
tion to the concentric to twin converter.

NOTE

Before cutting twin flue pipes ensure allowances
have been made for connection onto the previ-
ous piece and onto the concentric to twin con-
verter. The last twin flue pipes must be pushed
50mm onto the male spigots of the concentric to
twin converter.

You must ensure that the entire flue system is
properly supported and connected.

Ensure that any horizontal sections of pipe have
a 1° fall towards the appliance (17mm per
1000mm).

4.6

CONNECTING THE GAS AND WATER

The appliance is supplied with an accessories
pack that contains sealing washers and service
valves. The service valves are of the compression
type. When connecting pipe work to the valves,
tighten the compression end first then insert the
sealing washers before tightening the valve to the
appliance.

NOTE

It will be necessary to hold the valve with one
spanner whilst tightening with another.

4.6.1

GAS (fig. 6)

The appliance is supplied with a 15 mm service

Fig. 13

valve, connect a 15 mm pipe to the inlet of the
valve, and tighten both nuts.

NOTE

It will be necessary to calculate the diameter of the
gas pipe to ensure the appliance has an adequate
supply of gas.

4.6.2

FLOW & RETURN (fig. 6)

The appliance is supplied with 22 mm service
valves for the flow and return connections, connect
a 22 mm pipe to the inlet of each valve and tighten
both nuts.

4.6.3

SAFETY VALVE (fig. 6)

Connect the safety valve discharge pipe to the
safety valve outlet and tighten. The discharge pipe
must have a continuous fall away from the appli-
ance to outside and allow any water to drain away
thereby eliminating the possibility of freezing. The
discharge pipe must terminate in a position where
any water - possibly boiling - discharges safely
without causing damage or injury, but is still
visible.

4.7

ELECTRICAL CONNECTIONS

The electrical supply must be as specified in 3.7/
3.7a.  The appliance is supplied, pre-wired with a
1.0 metre length of flex, connect the wires as
follows:

connect the Brown wire to the L (Live) terminal
of the plug or fused isolator;

connect the Blue wire to the N (Neutral) terminal
of the plug or fused isolator;

connect the Green/Yellow wire to the E (Earth)
terminal of the plug or isolator;

ensure the plug or fused isolator is fitted with a
3AMP fuse.

If this method of connection is unsuitable, please
refer to section 8. A qualified electrician should
connect the electrical supply to the appliance. If
controls - external to the appliance - are required,
a competent person must undertake the design of
any external electrical circuits, please refer to
Section 8 for detailed instructions. ANY EXTER-
NAL CONTROL OR WIRING MUST BE SERVED
FROM THE SAME ISOLATOR AS THAT OF THE
APPLIANCE. The supply cable from the isolator
to the appliance must be 3-core flexible sized
0.75mm to BS 6500. Wiring to the appliance must
be rated for operation in contact with surfaces up
to 90ºC.

4.7.1

CASING REMOVAL

To gain access to the appliance electrical connec-
tions you must first remove the casing, proceed as
follows:

locate and remove the 3 screws that secure the
outer casing to the appliance (fig 14);

gently pull the right-hand side of the casing then
the left-hand to disengage it from the retaining
clips;

lift the casing upward to disengage it from the top
locating hooks and then remove;

store the casing and screws safely until re-
quired. Re-fit in the reverse order.

convertor box

condensate trap

Summary of Contents for Mynute

Page 1: ...Mynute 24m Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER...

Page 2: ...rical connections 13 Commissioning Page 5 1 Gas supply installation 15 5 2 The heating system 15 5 3 Initial filling of the system 15 5 4 Initial flushing of the system 15 5 5 Pre operation checks 15...

Page 3: ...ler which by design incorporates electronic ignition circulating pump expansion vessel safety valve pressure gauge and automatic by pass It is produced as a room sealed category II2H3 appliance suitab...

Page 4: ...tes Thereafter the boiler s output will either be increase to maximum or modulate to suit the setrequirement Whentheappliancereachesthedesiredtempera ture the burner will shut down and the boiler will...

Page 5: ...s Pre charge pressure 1 0 bar 2 4 Dimensions Height 740 mm Width 400 mm Depth 332 mm Dry weight 31 kg 2 5 Clearances Left side 12 mm Right side 12 mm Top 150 mm from casing or 25 mm above flue elbow w...

Page 6: ...Belowgutter drain pipe etc 75mm E Beloweaves 200mm F Below balcony car port roof etc 200mm G To the side of a soil drain pipe etc 150mm H Frominternal externalcornerorboundary 300mm I Aboveground roo...

Page 7: ...suit Details of essential features of compartment cup board design including airing cupboard installations are given in BS 6798 This appliance is not suitable for external installation BS5440 PART 1 F...

Page 8: ...ly this is sufficient however if the system has an unusually high water content it may be necessary to provide additional expansion capacity see 6 19 3 6 6 LOW PRESSURE SEALED SYSTEM An alternative me...

Page 9: ...The gas meter as supplied by the gas supplier must be checked to ensure that it is of adequate sizetodealwiththemaximumratedinputofallthe appliances that it serves Installation pipes must be fitted i...

Page 10: ...rgeneralguid ance only This appliance is a room sealed fan flued boiler consequently it does not require a permanent air vent for combustion air supply When installed in a cupboard or compartment vent...

Page 11: ...e only to the standard 60 100mm concentric flue system The appliance flue outlet elbow can be rotated through 360 on its vertical axis In addition the flue may be extended from the outlet elbow in the...

Page 12: ...irednumberofflueextensionsor bends uptothemaximumequivalentfluelength to the flue terminal using the clips screws and gaskets supplied fig 8 8A The interior trim should be fitted at this point Fig 8 B...

Page 13: ...given to the fact that there is the possibility of a small amountofcondensatedrippingfromtheterminal ensure that the entire flue system is adequately supported use at least one bracket for each extens...

Page 14: ...must always be level with or below that of the exhaust pipe Dependingonsiteconditionsitmaybepreferable to install the terminal assembly prior to fitting the twinfluepipes Markanddrilla130mmholeforthe...

Page 15: ...andreturnconnections connect a 22 mm pipe to the inlet of each valve and tighten both nuts 4 6 3 SAFETY VALVE fig 6 Connect the safety valve discharge pipe to the safetyvalveoutletandtighten Thedischa...

Page 16: ...ablethroughthecableanchorage fig 6 Connectthesupplycablewires earth live and neutral to their corresponding terminals on the terminal strip Ensure that the EARTH wire is left slightly longer that the...

Page 17: ...GHTING Ensure the electrical supply to the appliance is switchedon Switchthetimeclockorprogrammer iffitted toan on positionandensureallexternal controls are also calling for heat SECTION 5 COMMISSIONI...

Page 18: ...nty 5 13 INSTRUCTINGTHEUSER Hand over all documentation supplied with this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to...

Page 19: ...condition of the entire flue assembly Compare the results with the appliance design specification Any deterioration in performance must be identified and rectified without delay Ensurebothflueventuris...

Page 20: ...e electrical supply and attach a suitable manometer to the gas valve outlet test nipple Remove the compensator tube 7 3 1 SETTING THE MAXIMUM BURNER PRES SURE Light the boiler as described in 5 6 and...

Page 21: ...omponents may also assist in locating the fault 7 7 3 POLARITYCHECK With the appliance connected to the electrical supply and using a suitable multimeter carry out the following voltage tests connect...

Page 22: ...LS CN8 3 CN8 5 ON PCB NO NO YES MADE A LINK BETWEEN BLACK BLACK WIRES AT BOILER TERMINAL STRIP SWITCH ON BOILER AND SELECT MODE TO WINTER C H THERMOSTAT AT MAX YES LOOSE THE PUMP ACTING WITH A SCREWDR...

Page 23: ...HECK SUPPLY FUSE CONNECTORS TO BOILER TERMINALS MAINS BLUE BROWN WIRES AT BOILER STRIP NO REPLACE WIRING OR CONNECTIONS TERMINAL STRIP AND CONTROL BOARD YES YELLOW LED BLINKS CHIMNEY SWEEPER CYCLE RES...

Page 24: ...BETWEEN TERMINALS CN8 7 CN8 8 ON PCB NO YES NO CHECK WIRING AND CONNECTIONS NO DO THE AIR FLOW SWTCH TURN ON CHECK WIRING AND CONNECTIONS AIR FLOW SWITCH AND CONTROL BOARD YES NO ARE THE VENTURI TUBE...

Page 25: ...AND SELECT MODE TO WINTER C H THERMOSTAT AT MAX START RESTART THE TEST NO NO YES REPLACE WIRE AND CONNECTIONS REPLACE CONTROL BOARD REPLACE MODULATOR COIL IS THE RESISTENCE OF MODULATOR COIL ABOUT 70...

Page 26: ...R FLOW TEMPERATURE 80 C WAIT WATER FLOW TEMPERATURE 80 C NO YES REPLACE CONTROL BOARD REMOVE JUMPER IS TIMER JUMPER ON RESTART THE TEST DO BURNER AND FAN SWITCH ON OPEN THE LINK BETWEEN BLACK BLACK WI...

Page 27: ...ressure switch T L High limit thermostat P A Water pressure switch S R Primary NTC sensor JP1 Jumper CH only JP2 Setting timer JP3 Natural gas or LPG selector JP4 Jumper disable enable DHW absolut the...

Page 28: ...EGRALTIME CLOCK TheVokera integral time clock Part no 433 should be installed as shown in diagram 19B If a room thermostat is to be connected it should be of the voltage free type and must be con nect...

Page 29: ...Ignition module 10022174 20 Printed Circuit Board 10025340 21 Led Light Guide 10023816 26 Instrumental panel 10027015 27 Knob 10023818 28 Knob 10023817 31 Case 10023822 40 Door panel 10023810 61 Cover...

Page 30: ...lve 2907 23 Connection 10022499 27 Heating cock 1789 31 Venting plugs kit 01005137 63 Pipe 10020898 288 O ring 6898 289 Clip 2223 290 Clip 2165 300 Clip 2222 303 Connection 2217 353 Ogive 1824 400 Wir...

Page 31: ...e 10023603 3 Pump 10024573 7 Pipe 10022000 8 Heat exchanger 10023651 9 Pipe 10022002 12 Washer 2226 201 Washer 5026 285 NTC sensor 8484 289 Clip 2223 290 Clip 2165 299 Washer 10022726 417 Limit thermo...

Page 32: ...or manifold 10025271 4 Burner 10025270 5 Spark electrode 10025985 12 Pipe 10023996 13 Gas valve 10025074 14 Gas valve solenoid 10020838 15 Gas cock 10020897 16 Cover assembly 10024779 18 Glass 1002155...

Page 33: ...Lateral insulating panel 2231 4 Front insulating panel 2232 10 Fan 10020793 12 Connection 10021972 20 Fumes testing connection pipe 10021973 25 Pressure differential switch kit 01005272 28 Stop clip 1...

Page 34: ...e Thiswillensurethattheoutputoftheboiler burner pressure is not compromised due to a high flow temperature 10 5 2 SETTINGTHE MINIMUM BURNER PRESSURE Once the maximum burner pressure has been checked a...

Page 35: ...33 Mynute 24m...

Page 36: ...0 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to change the specifications...

Reviews: