background image

15

Mynute 24m

5.1

GAS SUPPLY INSTALLATION

Inspect the entire installation including the gas
meter, test for soundness and purge. Refer to BS
6891 for specific instruction.

5.2

THE HEATING SYSTEM

The appliance contains components that may
become damaged or rendered inoperable by oils
and/or debris that are residual from the installation
of the system, consequently it is essential that the
system be flushed in accordance with the follow-
ing instructions.

5.3

INITIAL FILLING OF THE SYSTEM

Ensure both flow and return service valves are
open, remove appliance casing as described in
4.7.1, identify the automatic air release valve and
loosen the dust cap by turning cap anticlockwise
one full turn. IMPORTANT, THERE ARE NO
MANUAL AIR RELEASE VALVES LOCATED ON
THE APPLIANCE. Ensure all manual air release
valves located on the heating system are closed.
Using the method of filling as described in fig. 5,
slowly proceed to fill the system. As water enters
the system the pressure gauge will begin to rise,
Once the gauge has reached 1 bar close the filling
valve and begin venting all manual air release
valves, starting at the lowest first. It may be
necessary to go back and top-up the pressure until
the entire system has been filled. Inspect the
system for water soundness, rectifying any leaks.

5.4

INITIAL FLUSHING

The whole of the heating system must be flushed
as detailed in 5.8. Open all radiator or heating
valves and the appliance flow and return service
valves. Drain the boiler and system from the
lowest points. Open the drain valve full bore to
remove any installation debris from the boiler prior
to lighting. Refill the boiler and heating system as
described in 5.3.

5.5

PRE-OPERATION CHECKS

Before attempting the initial lighting of the appli-
ance, the following checks must be carried out:

•••••

ensure all gas service valves from the meter to
the appliance are open and the supply pipe has
been properly purged;

•••••

ensure the proper electrical checks have been
carried out (section 7.7), particularly continuity,
polarity and resistance to earth;

•••••

ensure the 3-amp fuse - supplied with the appli-
ance - has been fitted;

•••••

ensure the system has been filled, vented and
the pressure set to 1bar;

•••••

ensure the flue system has been fitted properly
and in accordance with the instructions;

•••••

ensure all appliance service valves are open.

5.6

INITIAL LIGHTING

Ensure the electrical supply to the appliance is
switched on. Switch the time clock or programmer
(if fitted) to an “on” position and ensure all external
controls are also calling for heat.

SECTION 5      COMMISSIONING

Turn the mode selector knob to be “on” position
(fig. 1). The appliance will now go through an
ignition sequence as described in 1.2. Should the
appliance fail to ignite, refer to section 5.5 and/or
section 7 (fault finding).

5.7

CHECKING BURNER PRESSURES

Although the burner pressure is factory set, it is
necessary to check it during the commissioning.
Isolate the appliance from the electrical supply
and attach a suitable manometer to the gas valve
outlet test nipple (fig. 17). Light the boiler as
described in 5.6 and compare the reasging on the
manometer with the value described in 2.2. If
adjustment is required, follow the detailed instruc-
tions in section 7 (7.3). Once the burner pressure
has been checked, isolate the appliance from the
electrical supply, remove the manometer and
tighten the gas valve outlet test nipple.

5.8

FINAL FLUSHING OF THE HEATING SYSTEM

The system shall be flushed in accordance with
BS 7593. If a cleanser is to be used, it shall be from
a reputable manufacturer* and shall be adminis-
tered in strict accordance with the manufacturers
instructions.
*Both Sentinel and Fernox manufacture products
that have proved suitable for use with Vokera ap-
pliances. Vokera Ltd. cannot comment on the suit-
ability of any other such product with our appli-
ance.

5.8.1

INHIBITORS

See 3.8.

5.9

SETTING THE BOILER OPERATING TEMPERA-
TURE

The flow outlet temperature can be adjusted be-
tween 40ºC - 80ºC via the thermostat knob (fig.1).

5.10

SETTING THE SYSTEM DESIGN PRESSURE

The design pressure should be a minimum of 1 bar
and a maximum of 1.5 bar.
The actual reading should ideally be 1 bar plus the
equivalent height in metres (0.1 BAR = 1 metre) to
the highest point in the system above the base of
the appliance (up to the maximum of 1.5 BAR
total).
N.B. The safety valve is set to lift at 3 BAR/
30metres/ 45psig.
To lower the system pressure to the required
value, pull lever on head of safety valve to release
water until the required figure registers on the
pressure gauge (fig.1).

5.11

REGULATING THE CENTRAL HEATING SYS-
TEM

Fully open all radiator and circuit valves and run
the appliance for both heating and hot water until
heated water is circulating. If conditions are warm
remove any thermostatic valve heads. Adjust
radiator return valves and any branch circuit return
valves until the individual return temperatures are
correct and are approximately equal.

Summary of Contents for Mynute

Page 1: ...Mynute 24m Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER...

Page 2: ...rical connections 13 Commissioning Page 5 1 Gas supply installation 15 5 2 The heating system 15 5 3 Initial filling of the system 15 5 4 Initial flushing of the system 15 5 5 Pre operation checks 15...

Page 3: ...ler which by design incorporates electronic ignition circulating pump expansion vessel safety valve pressure gauge and automatic by pass It is produced as a room sealed category II2H3 appliance suitab...

Page 4: ...tes Thereafter the boiler s output will either be increase to maximum or modulate to suit the setrequirement Whentheappliancereachesthedesiredtempera ture the burner will shut down and the boiler will...

Page 5: ...s Pre charge pressure 1 0 bar 2 4 Dimensions Height 740 mm Width 400 mm Depth 332 mm Dry weight 31 kg 2 5 Clearances Left side 12 mm Right side 12 mm Top 150 mm from casing or 25 mm above flue elbow w...

Page 6: ...Belowgutter drain pipe etc 75mm E Beloweaves 200mm F Below balcony car port roof etc 200mm G To the side of a soil drain pipe etc 150mm H Frominternal externalcornerorboundary 300mm I Aboveground roo...

Page 7: ...suit Details of essential features of compartment cup board design including airing cupboard installations are given in BS 6798 This appliance is not suitable for external installation BS5440 PART 1 F...

Page 8: ...ly this is sufficient however if the system has an unusually high water content it may be necessary to provide additional expansion capacity see 6 19 3 6 6 LOW PRESSURE SEALED SYSTEM An alternative me...

Page 9: ...The gas meter as supplied by the gas supplier must be checked to ensure that it is of adequate sizetodealwiththemaximumratedinputofallthe appliances that it serves Installation pipes must be fitted i...

Page 10: ...rgeneralguid ance only This appliance is a room sealed fan flued boiler consequently it does not require a permanent air vent for combustion air supply When installed in a cupboard or compartment vent...

Page 11: ...e only to the standard 60 100mm concentric flue system The appliance flue outlet elbow can be rotated through 360 on its vertical axis In addition the flue may be extended from the outlet elbow in the...

Page 12: ...irednumberofflueextensionsor bends uptothemaximumequivalentfluelength to the flue terminal using the clips screws and gaskets supplied fig 8 8A The interior trim should be fitted at this point Fig 8 B...

Page 13: ...given to the fact that there is the possibility of a small amountofcondensatedrippingfromtheterminal ensure that the entire flue system is adequately supported use at least one bracket for each extens...

Page 14: ...must always be level with or below that of the exhaust pipe Dependingonsiteconditionsitmaybepreferable to install the terminal assembly prior to fitting the twinfluepipes Markanddrilla130mmholeforthe...

Page 15: ...andreturnconnections connect a 22 mm pipe to the inlet of each valve and tighten both nuts 4 6 3 SAFETY VALVE fig 6 Connect the safety valve discharge pipe to the safetyvalveoutletandtighten Thedischa...

Page 16: ...ablethroughthecableanchorage fig 6 Connectthesupplycablewires earth live and neutral to their corresponding terminals on the terminal strip Ensure that the EARTH wire is left slightly longer that the...

Page 17: ...GHTING Ensure the electrical supply to the appliance is switchedon Switchthetimeclockorprogrammer iffitted toan on positionandensureallexternal controls are also calling for heat SECTION 5 COMMISSIONI...

Page 18: ...nty 5 13 INSTRUCTINGTHEUSER Hand over all documentation supplied with this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to...

Page 19: ...condition of the entire flue assembly Compare the results with the appliance design specification Any deterioration in performance must be identified and rectified without delay Ensurebothflueventuris...

Page 20: ...e electrical supply and attach a suitable manometer to the gas valve outlet test nipple Remove the compensator tube 7 3 1 SETTING THE MAXIMUM BURNER PRES SURE Light the boiler as described in 5 6 and...

Page 21: ...omponents may also assist in locating the fault 7 7 3 POLARITYCHECK With the appliance connected to the electrical supply and using a suitable multimeter carry out the following voltage tests connect...

Page 22: ...LS CN8 3 CN8 5 ON PCB NO NO YES MADE A LINK BETWEEN BLACK BLACK WIRES AT BOILER TERMINAL STRIP SWITCH ON BOILER AND SELECT MODE TO WINTER C H THERMOSTAT AT MAX YES LOOSE THE PUMP ACTING WITH A SCREWDR...

Page 23: ...HECK SUPPLY FUSE CONNECTORS TO BOILER TERMINALS MAINS BLUE BROWN WIRES AT BOILER STRIP NO REPLACE WIRING OR CONNECTIONS TERMINAL STRIP AND CONTROL BOARD YES YELLOW LED BLINKS CHIMNEY SWEEPER CYCLE RES...

Page 24: ...BETWEEN TERMINALS CN8 7 CN8 8 ON PCB NO YES NO CHECK WIRING AND CONNECTIONS NO DO THE AIR FLOW SWTCH TURN ON CHECK WIRING AND CONNECTIONS AIR FLOW SWITCH AND CONTROL BOARD YES NO ARE THE VENTURI TUBE...

Page 25: ...AND SELECT MODE TO WINTER C H THERMOSTAT AT MAX START RESTART THE TEST NO NO YES REPLACE WIRE AND CONNECTIONS REPLACE CONTROL BOARD REPLACE MODULATOR COIL IS THE RESISTENCE OF MODULATOR COIL ABOUT 70...

Page 26: ...R FLOW TEMPERATURE 80 C WAIT WATER FLOW TEMPERATURE 80 C NO YES REPLACE CONTROL BOARD REMOVE JUMPER IS TIMER JUMPER ON RESTART THE TEST DO BURNER AND FAN SWITCH ON OPEN THE LINK BETWEEN BLACK BLACK WI...

Page 27: ...ressure switch T L High limit thermostat P A Water pressure switch S R Primary NTC sensor JP1 Jumper CH only JP2 Setting timer JP3 Natural gas or LPG selector JP4 Jumper disable enable DHW absolut the...

Page 28: ...EGRALTIME CLOCK TheVokera integral time clock Part no 433 should be installed as shown in diagram 19B If a room thermostat is to be connected it should be of the voltage free type and must be con nect...

Page 29: ...Ignition module 10022174 20 Printed Circuit Board 10025340 21 Led Light Guide 10023816 26 Instrumental panel 10027015 27 Knob 10023818 28 Knob 10023817 31 Case 10023822 40 Door panel 10023810 61 Cover...

Page 30: ...lve 2907 23 Connection 10022499 27 Heating cock 1789 31 Venting plugs kit 01005137 63 Pipe 10020898 288 O ring 6898 289 Clip 2223 290 Clip 2165 300 Clip 2222 303 Connection 2217 353 Ogive 1824 400 Wir...

Page 31: ...e 10023603 3 Pump 10024573 7 Pipe 10022000 8 Heat exchanger 10023651 9 Pipe 10022002 12 Washer 2226 201 Washer 5026 285 NTC sensor 8484 289 Clip 2223 290 Clip 2165 299 Washer 10022726 417 Limit thermo...

Page 32: ...or manifold 10025271 4 Burner 10025270 5 Spark electrode 10025985 12 Pipe 10023996 13 Gas valve 10025074 14 Gas valve solenoid 10020838 15 Gas cock 10020897 16 Cover assembly 10024779 18 Glass 1002155...

Page 33: ...Lateral insulating panel 2231 4 Front insulating panel 2232 10 Fan 10020793 12 Connection 10021972 20 Fumes testing connection pipe 10021973 25 Pressure differential switch kit 01005272 28 Stop clip 1...

Page 34: ...e Thiswillensurethattheoutputoftheboiler burner pressure is not compromised due to a high flow temperature 10 5 2 SETTINGTHE MINIMUM BURNER PRESSURE Once the maximum burner pressure has been checked a...

Page 35: ...33 Mynute 24m...

Page 36: ...0 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to change the specifications...

Reviews: