03TA Service Manual
TROUBLESHOOTING
2/14/07
8-10
SYMPTOM: High head pressure (Air-cooled machine).
POSSIBLE CAUSE
POSSIBLE REMEDY
Condenser
fan(s)
not
running.
Defective motor, fan control switch, fan
contactor. Replace defective part. Check
condenser fan disconnect for thrown switch,
or blown fuse. Replace fuse and reset switch.
If the condenser is split, check the normally
open solenoid valve to make sure it is open;
also check the fan sequencing thermostats and
fan motor contactors to make sure they are
functioning properly. Replace any defective
parts.
Dirty condenser causing restricted airflow.
Visually inspect condenser and clean as
necessary.
Non-condensables (usually air) in the system.
Follow same procedure as specified for
removing non-condensables from Water
Cooled
machine
, except
evacuate the air-
cooled condenser also.
Summary of Contents for TUBE-ICE 03TA
Page 10: ...5 24 11 Blank page ...
Page 14: ...03TA Service Manual INTRODUCTION 4 21 14 1 4 FIGURE 1 1 Assembly Air Cooled Front View ...
Page 15: ...03TA Service Manual INTRODUCTION 4 21 14 1 5 FIGURE 1 2 Assembly Air Cooled Rear View ...
Page 16: ...03TA Service Manual INTRODUCTION 4 21 14 1 6 FIGURE 1 3 Assembly Air Cooled Right Side View ...
Page 17: ...03TA Service Manual INTRODUCTION 4 21 14 1 7 FIGURE 1 4 Assembly Water Cooled Front View ...
Page 18: ...03TA Service Manual INTRODUCTION 4 21 14 1 8 FIGURE 1 5 Assembly Water Cooled Rear View ...
Page 19: ...03TA Service Manual INTRODUCTION 4 21 14 1 9 FIGURE 1 6 Assembly Water Cooled Right Side View ...
Page 20: ...03TA Service Manual INTRODUCTION 4 21 14 1 10 BLANK ...
Page 44: ...5 24 11 Blank page ...
Page 54: ...5 24 11 Blank page ...
Page 104: ...5 24 11 Blank page ...
Page 112: ...5 24 11 Blank page ...