Wiring and Electrical Connection
! WARNING !
Only service personnel experienced in refrigeration and qualified to work with high voltage
electrical equipment should be allowed to install or work on the Tube-Ice
®
machine.
! WARNING !
Refer to TABLE 3-2 below to properly size wiring connections. A fused disconnect must be
provided near the Tube-Ice
®
machine. Connect 3 phase power, L1, L2, L3 to the power distribution
block (PDB) for operation of the Tube-Ice
®
machine and its controls. Rotation checking of cutter
motor and water pump is required (see following section). Also, if one leg of the 3 phase power is
higher or lower (“Wild”), then it should be connected to terminal #L2. Connect the “Ground” wire
to the “Ground” lug provided.
FIGURE 3-6
Control Panel Power Connections
Standard Voltages
Water Cooled
Air Cooled
F.L.A.
Min.
Ampacity
Max. Fuse
F.L.A.
Min.
Ampacity
Max. Fuse
208/230, 3ph, 60 Hz
48.3
58.6
100
54.3
64.6
110
460, 3ph, 60 Hz
23.7
28.7
50
26.4
31.4
55
200, 3ph, 50 Hz
50.9
61.8
110
57.5
68.4
115
400, 3ph, 50 Hz
24.2
30.4
55
27.2
32.2
55
TABLE 3-2
Electrical Specifications
AUX CONNECTIONS
Cutter Motor, Pump Motor &
Compressor Interlocks
MAIN MACHINE POWER
Incoming power to be connected to
Power Distribution Block (PDB)
AIR COOLED CONDENSER
CONNTECTIONS
Power for Fan Motors (B7, B8 & B9)
AIR COOLED CONDENSER CONNTECTIONS
Power for Condenser control circuit (11 & 22)
Summary of Contents for TUBE-ICE 03TA
Page 10: ...5 24 11 Blank page ...
Page 14: ...03TA Service Manual INTRODUCTION 4 21 14 1 4 FIGURE 1 1 Assembly Air Cooled Front View ...
Page 15: ...03TA Service Manual INTRODUCTION 4 21 14 1 5 FIGURE 1 2 Assembly Air Cooled Rear View ...
Page 16: ...03TA Service Manual INTRODUCTION 4 21 14 1 6 FIGURE 1 3 Assembly Air Cooled Right Side View ...
Page 17: ...03TA Service Manual INTRODUCTION 4 21 14 1 7 FIGURE 1 4 Assembly Water Cooled Front View ...
Page 18: ...03TA Service Manual INTRODUCTION 4 21 14 1 8 FIGURE 1 5 Assembly Water Cooled Rear View ...
Page 19: ...03TA Service Manual INTRODUCTION 4 21 14 1 9 FIGURE 1 6 Assembly Water Cooled Right Side View ...
Page 20: ...03TA Service Manual INTRODUCTION 4 21 14 1 10 BLANK ...
Page 44: ...5 24 11 Blank page ...
Page 54: ...5 24 11 Blank page ...
Page 104: ...5 24 11 Blank page ...
Page 112: ...5 24 11 Blank page ...