19
3) Example: ACP-56COFM164GEEI
Serial No.
Model
Indoor unit 1
Cassette type
ACP-12CCIFM35GEEI
Indoor unit 2
Duct type
ACP-09DTIFM25GEEI
Indoor unit 3
Wall mounted type
ACP-09CIFM25GEEI
Indoor unit 4
Duct type
ACP-09DTIFM25GEEI
Indoor unit 5
Duct type
ACP-09DTIFM25GEEI
Indoor unit 6
Wall mounted type
ACP-09CIFM25GEEI
Table 7
Serial No.
Diameter(mm)
Length(m)
L1
Φ9.52
20
L2
Φ9.52
10
L4
Φ9.52
10
1A
Φ6.35
5
1B
Φ6.35
5
1C
Φ6.35
5
2A
Φ6.35
5
2B
Φ6.35
5
2C
Φ6.35
5
Fig. 19
Table 6
The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m). Thus, the total
length is over than 30m, so the air conditioner needs to add refrigerant.
♦ Additional refrigerant charge