22
Note:
♦ The total length of the transmission line between the outdoor unit and the furthest BU
module is not more than 55m. Otherwise, the system cannot work possibility.
♦ The specifications of the power cable and transmission line listed in the table above are
determined based on the maximum power (maximum amps) of the unit.
♦ The specifications of the power cable listed in the table above are applied to the
7 Electrical Wiring Work
7.1
Wiring Connection
Phase and frequency
3Ph,50Hz
Voltage
380~415V
Recommended cable of outdoor unit
(Pieces x Sectional area)
ACP-48COFM140GEEI
5x2.5 mm
2
ACP-56COFM164GEEI
Recommended cable of BU module
(Pieces x Sectional area)
3x0.75 mm
2
Transmission line (Pieces x Sectional area) 2x1.0 mm
2
Recommended cable of indoor unit
(Pieces x Sectional area)
4x0.75mm
2
Capacity of the air switch
ACP-48COFM140GEEI
25A
ACP-56COFM164GEEI
25A
Fig. 21
7.2 Requirements of Power Circuit and Cable
Table 9
Summary of Contents for ACP-48COFM140GEEI
Page 1: ...Upute za uporabu User manual ACP 56COFM164GEEI ACP 48COFM140GEEI RoHS 14 ...
Page 2: ...ENG User manual RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Page 13: ...8 4 2 Outline Dimension of Outdoor Unit Fig 3 mm ...
Page 17: ...12 3 For three BU modules there will not be more than nine indoor units Fig 10 ...
Page 42: ...HR BiH Upute za uporabu RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Page 53: ...8 4 2 Nacrt dimenzija vanjske jedinice Sl 3 mm ...
Page 57: ...12 3 Za tri BU modula gdje neće biti više od devet unutarnjih jedinica Sl 10 ...
Page 83: ......
Page 87: ......
Page 93: ...3 4 ...
Page 100: ...3 4 3 4 3 4 ...
Page 109: ...www vivax com ...
Page 110: ...www vivax com ...