14
6.3
Dimension of Connecting Pipe
Table 4
Sorts
Gas Pipe
(mm)
Liquid Pipe
(mm)
Capacity of indoor
unit(Btu/h)
7000,9000,12000
Φ9.52
Φ6.35
18000
Φ12.7
Φ6.35
21000,24000
Φ15.9
Φ9.52
Outdoor unit
ACP-48COFM140GEEI
Φ15.9
Φ9.52
ACP-56COFM164GEEI
Φ15.9
Φ9.52
Between outdoor unit
and the 1st branch
The pipe L1
Φ19.05
Φ9.52
Between the 1st and the
2nd branch
The pipe L2
Φ15.9
Φ9.52
6.4
Connection of Branch Pipe
1) If two or three BU modules used, Y-type branch pipe of FQ01A/A will be chosen.
FQ01A/A (Liquid pipe)
FQ01A/A (Gas pipe)
Fig. 12
2) Y-type branch pipe is equipped with auxiliary tubes to adjust the diameter of different pipes. If
the dimension of the pipe selected is different from the dimension of branch pipe joint, Cut the
copper tube in the middle with tube cutter and clear up burrs. Please do that as following
figure.
Fig. 13
3) Y-type branch pipe must be installed in vertical or horizontal direction. In the inlet of the
branch pipe, keep at least 500mm straight pipe.
Summary of Contents for ACP-48COFM140GEEI
Page 1: ...Upute za uporabu User manual ACP 56COFM164GEEI ACP 48COFM140GEEI RoHS 14 ...
Page 2: ...ENG User manual RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Page 13: ...8 4 2 Outline Dimension of Outdoor Unit Fig 3 mm ...
Page 17: ...12 3 For three BU modules there will not be more than nine indoor units Fig 10 ...
Page 42: ...HR BiH Upute za uporabu RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Page 53: ...8 4 2 Nacrt dimenzija vanjske jedinice Sl 3 mm ...
Page 57: ...12 3 Za tri BU modula gdje neće biti više od devet unutarnjih jedinica Sl 10 ...
Page 83: ......
Page 87: ......
Page 93: ...3 4 ...
Page 100: ...3 4 3 4 3 4 ...
Page 109: ...www vivax com ...
Page 110: ...www vivax com ...