6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Connective pipe length
Air purging
Additional amount of
refrigerant
All
Less than 5m
Use vacuum pump
------------------
ALL
More than 5m
Use vacuum pump
(Pipe length
–
5)
×
20g/m
Model
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
5
8
20
ACP-18CH50AEF, ACP-18CH50AEG
5
10
25
ACP-09CH25AEF, ACP-09CH25AEG
ACP-12CH35AEF, ACP-12CH35AEG
ACP-18CH50AEF, ACP-18CH50AEG
ACP-24CH70AEG
ACP-09CH25AEF, ACP-09CH25AEG
ACP-12CH35AEF, ACP-12CH35AEG
ACP-24CH70AEG
5
10
20
Caution:
Capacity test is based on standard length and maximum allowance length is based on system
reliability.
Oil trap should be installed per 5-7 meters.