29
The auto fan:
8.4.2.4 Evaporator low temperature T2 protection.
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and outdoor
fan will shut off.
When T2 is higher than TE6, the compressor and outdoor fan will restart up.
While TE5=4°C TE6=10°C for
,
ACP-09CH25AEF, ACP-09CH25AEG, ACP-12CH35AEF,
8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
Everytime the compressors start up, they will keep running for
+
t minutes(protections are active) and
then follow the below rules. (While
+
t=7.)
When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is
lower than Tk, the compressor and outdoor fan will start up.
ACP-12CH35AEG models.
While TE5=3°C TE6=14°C for
,
ACP-18CH50AEF, ACP-18CH50AEG models.
Tj=Ts+3 Tk=Ts+2.