Defrosting action
:
About the setting defrosting time:
(1) Condition 1 of defrosting;
If case B happens before case A and lasts till case A happens, the setting defrosting time is 10
minutes.Otherwise the defrosting time is 7.5 minutes.
(2) Condition 2 of defrosting.
The defrosting time is 10 minutes.
l
No matter what condition of defrosting is, if the defrosting time keeps 7.5 minutes for 3 times, it will
be 10 minutes in the 4
th
defrosting.
8.4.3.5 High evaporator coil temp.T2 protection:
For 7k,9k,18k models:
While TE7=60°C,TE8=53°C,TE9=50°C for
ACP-09CH25AEF, ACP-09CH25AEG models,
TE7=63°C,TE8=53°C,TE9=52°C for
ACP-12CH35AEF, ACP-12CH35AEG models,
TE7=60°C,TE8=52°C,TE9=51°C for
ACP-18CH50AEF, ACP-18CH50AEG models.