Outputs and Digital Input
Configuring Analog Output
VT400 Technical Manual, Rev. A5
54
Doc
#
UM-VT400-EN
Par. Description
Values
A.3
Error output level
. Specifies whether scale errors should be
indicated as a low or high signal.
0 = Low (0mA)
1 = High (24mA)
A.4
Current / voltage
. This parameter must correspond to the
hardware jumper, which defines whether output should be in
current or voltage (see section
7.4.1). The default setting is
voltage (1).
0 = Current
1 = Voltage
A.5
Net / gross
. Specifies whether the indicator should always
output gross weight, or output net weight when tare is active.
0 = Net weight
1 = Gross weight
A.6
Effective range for current output
. Sets the range to 0-
20mA or 4-20mA. Relevant only if A.4 and the hardware
jumper are set to current.
0 = 0-20mA
1 = 4-20mA
A.7
Resolution
. Specifies whether output should be in high
resolution if the display is showing high resolution.
0 = Display
1 = Internal
A.8
Operation
. Enables and disables the analog output.
0 = Disabled
1 = Enabled