Chapter 3 Deployment
Manual VIPA System SLIO
3-70
HB300E - IM - RE_053-1CA00 - Rev. 11/29
Index
Sub-
Index
Name
Type
Attr. Map. Default value Meaning
0x6443 0x00 Analog
output
block
Unsigned8 ro N Depending
on the com-
ponents fitted
Number of available analog
outputs
0x01
1.
analog
output block
Unsigned8
rw
N
0xFF
1. error mode analog output
block
...
...
...
...
...
...
...
0xFE
254.
analog
output block
Unsigned8
rw
N
0xFF
254. error mode analog output
block
This object indicates whether an output is set to a pre-defined error value
(set in object 0x6444) in case of an internal device failure.
0 = current value
1 = set to error value 0x6444
Index
Sub-
Index
Name
Type
Attr. Map. Default value Meaning
0x6444 0x00 16bit
digital
input block
Unsigned8 ro N Depending
on
the compo-
nents fitted
Number of available analog
output blocks
0x01
1. analog block Unsigned16
rw
N
0x0000
1. analog output block
...
...
...
...
...
...
...
0xFE
254.
analog
block
Unsigned16
rw
N
0x0000
254. analog output block
Presupposed that the corresponding error (0x6443) is active, device
failures set the output to the value configured by this object.
Analog output error
mode
Analog output error
value