Manual VIPA System SLIO
Chapter 1 Basics and Assembly
HB300E - IM - RE_053-1CA00 - Rev. 11/29
1-15
DC24V
0V
DC24V
0V
1
2
DC24V max. 10A
SysDC5V max. 3A
(1) DC 24V for power section supply I/O area (max 10A)
(2) DC 24V for electronic power supply bus coupler and I/O area
Attention!
Since the power section supply is not internally protected, it is to be
externally protected with a fuse, which corresponds to the maximum
current. This means max. 10A is to be protected by a 10A fuse (fast)
respectively by a line circuit breaker 10A characteristics Z!
Note!
The electronic power section supply is internally protected against higher
voltage by fuse. The fuse is within the power module.
If the fuse releases, its electronic module must be exchanged!
•
The power section supply is to be externally protected with a fuse, which
corresponds to the maximum current. This means max. 10A is to be
protected with a 10A fuse (fast) respectively by a line circuit breaker 10A
characteristics Z!
•
It is recommended to externally protect the electronic power supply for
bus coupler and I/O area with a 2A fuse (fast) respectively by a line
circuit breaker 2A characteristics Z.
•
The electronic power supply for the I/O area of the power module 007-
1AB10 should also be externally protected with a 1A fuse (fast)
respectively by a line circuit breaker 1A characteristics Z.
After PowerON of the System SLIO the LEDs RUN respectively MF get on
so far as the sum current does not exceed 3A.
With a sum current greater than 3A the LEDs may not be activated. Here
the power module with the order number 007-1AB10 is to be placed
between the peripheral modules. More concerning this may be found at the
following page.
Standard wiring
Fusing
State of the
electronic power
supply via LEDs