Manual VIPA System 300S SPEED7
Chapter 1 Basics
HB140E - CP - RE_341-2CH71 - Rev. 09/46
1-5
The SPEED-Bus is a 32Bit parallel bus developed from VIPA with a
maximum data rate of 40MByte/s. Via the SPEED-Bus you may connect up
to 10 SPEED-Bus modules to your CPU 31xS.
In opposite to the "standard" backplane bus where the modules are
plugged-in at the right side of the CPU by means of single bus connectors,
the modules at the SPEED-Bus are plugged-in at the left side of the CPU
via a special SPEED-Bus rail.
VIPA delivers profile rails with integrated SPEED-Bus for 2, 6 or 10
SPEED-Bus peripheral modules with different lengths.
The SPEED-Bus peripheral modules may exclusively plugged at the
SPEED-Bus slots at the left side of the CPU. The following SPEED-Bus
modules are in preparation:
•
Fast fieldbus modules like Profibus DP, Interbus, CANopen master and
CANopen slave
•
Fast CP 343 (CP 343 Communication processor for Ethernet)
•
Fast CP 341 with double RS 422/485 interface
•
Fast digital input-/output modules (Fast Digital IN/OUT)
Every CPU 31xS has an integrated work memory. During program run the
total memory is divided into 50% for program code and 50% for data.
Starting with CPU firmware 3.0.0 there is the possibility to extend the total
memory to its maximum by means of a MCC memory extension card.
The CPUs of the System 300S series with SPEED-Bus have an integrated
Profibus DP master. Via the DP master with a data range of 1kByte for in-
and output you may address up to 124 DP slaves.
The project engineering takes place in WinPLC7 from VIPA or in the
hardware configurator from Siemens.
Every CPU 31xS has an Ethernet interface for PG/OP communication. Via
the "PLC" functions you may directly access the Ethernet PG/OP channel
and program res. remote control your CPU. A max. of 2 PG/OP
connections is available.
You may also access the CPU with a visualization software via these
connections.
SPEED-Bus
SPEED-Bus
peripheral
modules
Memory
management
Integrated
Profibus
DP master
Integrated
Ethernet PG/OP
channel
Summary of Contents for CP 341S
Page 1: ...VIPA System 300S SPEED7 CP 341 2CH71 Manual HB140E_CP RE_341 2CH71 Rev 09 46 November 2009 ...
Page 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_341 2CH71 Rev 09 46 ...
Page 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_341 2CH71 Rev 09 46 ...
Page 70: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_341 2CH71 Rev 09 46 M Stich ...