Chapter 3 Deployment
Manual VIPA TM
3-28
HB39E - TM - RE_900-2H611 - Rev. 10/16
For the further approach it is precondition that you have access to the Web
page of the Teleservice module, your PLC may be reached via the TM and
the corresponding
Topics
are configured.
•
Open the Web page of the Teleservice module.
•
Navigate via
Configuration
>
Tag setup
to the page "Create new Tag ...".
•
Enter the following parameters:
Tag name
:
Test
Server name
: S73&400
Topic name
:
A
Address
:
MW0
Type
:
Boolean
•
Otherwise leave the standard setting and click at [Add/Update...].
•
Switch with
Main menu
>
View I/O
to the Tag list.
•
Enter a new value for the Tag "Test" and click at [Update]. Now this
value is set and may be transferred to the CPU with clicking to [Update]
in the headline.
•
If the new value is accepted by the CPU, so the communication between
the TM and the CPU is secured.
•
Open the Web page of the Teleservice module.
•
Navigate via
Configuration
>
Tag setup
to the page "Create new Tag ...".
•
Enter the following parameters:
Tag Name
:
TM_Input res. TM_Output
Server Name
: TM
TM
Topic Name
:
remains free
remains free
Adresse
:
DI1
DO1
Typ
:
Digital
Digital
•
Otherwise leave the standard setting and click at [Add/Update...].
Here also the input may be read respectively the output may be written by
means of the Tag list.
Examples
Accessing data
in the PLC
Access via View I/O
Accessing the I/Os
of the TM
Access via View I/O
Summary of Contents for 900-2H611
Page 4: ...Contents Manual VIPA TM ii HB39E TM RE_900 2H611 Rev 10 16...
Page 8: ...Safety information Manual VIPA TM 4 HB39E TM RE_900 2H611 Rev 10 16...
Page 70: ...Chapter 3 Deployment Manual VIPA TM 3 44 HB39E TM RE_900 2H611 Rev 10 16...
Page 72: ...Index Manual VIPA TM A 2 HB39E TM RE_900 2H611 Rev 10 16 M Stich...