![VIPA 900-2H611 Manual Download Page 16](http://html1.mh-extra.com/html/vipa/900-2h611/900-2h611_manual_1029227016.webp)
Chapter 1 Assembly and installation guidelines
Manual VIPA TM
1-8
HB39E - TM - RE_900-2H611 - Rev. 10/16
In the most times it is enough to take care of some elementary rules to
guarantee the EMC. Please regard the following basic rules when installing
your PLC.
•
Take care of a correct area-wide grounding of the inactive metal parts
when installing your components.
- Install a central connection between the ground and the protected
earth conductor system.
- Connect all inactive metal extensive and impedance-low.
- Please try not to use aluminum parts. Aluminum is easily oxidizing
and is therefore less suitable for grounding.
•
When cabling, take care of the correct line routing.
- Organize your cabling in line groups (high voltage, current supply,
signal and data lines).
- Always lay your high voltage lines and signal res. data lines in
separate channels or bundles.
- Route the signal and data lines as near as possible beside ground
areas (e.g. suspension bars, metal rails, tin cabinet).
•
Proof the correct fixing of the lead isolation.
- Data lines must be laid isolated.
- Analog lines must be laid isolated. When transmitting signals with
small amplitudes the one sided laying of the isolation may be
favorable.
- Lay the line isolation extensively on an isolation/protected earth con-
ductor rail directly after the cabinet entry and fix the isolation with
cable clamps.
- Make sure that the isolation/protected earth conductor rail is
connected impedance-low with the cabinet.
- Use metallic or metalized plug cases for isolated data lines.
•
In special use cases you should appoint special EMC actions.
- Wire all inductivities with erase links, which are addressed by your
PLC.
- For lightening cabinets you should prefer incandescent lamps and
avoid luminescent lamps.
•
Create a homogeneous reference potential and ground all electrical
operating supplies when possible.
- Please take care for the targeted employment of the grounding
actions. The grounding of the PLC is a protection and functionality
activity.
- Connect installation parts and cabinets with your PLC in star topology
with the isolation/protected earth conductor system. So you avoid
ground loops.
- If potential differences between installation parts and cabinets occur,
lay sufficiently dimensioned potential compensation lines.
Basic rules for
EMC
Summary of Contents for 900-2H611
Page 4: ...Contents Manual VIPA TM ii HB39E TM RE_900 2H611 Rev 10 16...
Page 8: ...Safety information Manual VIPA TM 4 HB39E TM RE_900 2H611 Rev 10 16...
Page 70: ...Chapter 3 Deployment Manual VIPA TM 3 44 HB39E TM RE_900 2H611 Rev 10 16...
Page 72: ...Index Manual VIPA TM A 2 HB39E TM RE_900 2H611 Rev 10 16 M Stich...