Manual VIPA System SLIO
Chapter 2 Hardware description
HB300E - IM - RE_053-1EC00 - Rev. 11/03
2-3
Structure
13
1
5
7
8
11
4
2
3
6
10
12
9
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
Locking lever terminal module
Labeling strip bus interface
LED status indication bus interface
Labeling strip power module
LED status indication power module
Backplane bus
DC 24V power section supply
Power module
EtherCAT RJ45 bus interface "IN"
EtherCAT RJ45 bus interface "OUT"
Unlocking lever power module
Bus interface
Terminal
LED
Color
Description
PW green
●
Bus interface is power supplied
SF red
☼
1 flash per s:
With state change due to an error
e.g. a module is removed
2 flashes per s:
At EtherCAT-Timeout
(watchdog) e.g. EtherCAT master is missing
Blinks with 2Hz:
At error in configuration
RUN green
○
Bus coupler in state Init
●
Bus coupler in state Operational
☼
Blinking with 2Hz:
Bus coupler in state Pre-Operational
1 flash per s:
Bus coupler in state Safe Operational
L/A1 green
○
No communication to the preceding station
●
Preceding EtherCAT station is connected
IF1 red
●
Internal error during communication with the
preceding station
L/A2 green
○
No communication to the succeeding station
●
Succeeding EtherCAT station is connected
Status indication
bus interface
PW
SF
RUN
L/A1
IF1
L/A2
IF2
IF2 red
●
Internal error during communication with the
succeeding EtherCAT station
on:
●
off:
○
blinking:
☼
053-1EC00
Summary of Contents for 053-1EC00
Page 1: ...VIPA System SLIO IM 053 1EC00 Manual HB300E_IM RE_053 1EC00 Rev 11 03 January 2011...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1EC00 Rev 11 03...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1EC00 Rev 11 03...
Page 60: ...Chapter 3 Deployment Manual VIPA System SLIO 3 28 HB300E IM RE_053 1EC00 Rev 11 03...