57
3.
And mostly important is, that total number (sum) of interfaces and meters, per
d
ata
logger can be 5 devices. So, if to one interface you connect 4 meters, you can use 1 more
interface, but to this interface you can connect only 1 meter, because 4+1 is 5 (MAX
number) – you can’t connect one more meter to any interface!
To
CONFIGURATE
HEAT meters, you need to setup (see
1.
Number of interfaces;
2.
Interface settings:
a)
COM client (UART port must be configured and assigned to COM client, how
to do this, see chapter
7.7
);
b)
Type of meter’s (choose from the list of supported meters, or contact
manufacturer);
c)
Amount of meters, that you connect to this interface;
d)
Data read mode, “Periodically” or “In set time”;
e)
Read period (min), if in previous section you selected “Periodically”, now you
need to set reading period in minutes, the value can be from 1 to 720 minutes
(be default it is 120 min). If “Reading mode” is set to “In set time”, this value is
not important, because it is not used;
f)
In Address1 .. Address5 fields, you need to enter address of each connected
meter (some address values is set by meter manufacturer, some models support
custom addresses, read meter’s manual, to get more information);
g)
If in “Read mode” you choose “In set time, then in right part appears “Data read
time” table, you must enter up to 6 data read from meter times.
Summary of Contents for MX-7
Page 1: ...2 ...
Page 4: ...5 9 6 USB cable 85 9 7 Installing VILTRUS USB driver 85 9 8 TCP IP settings 87 ...
Page 22: ...23 see Pic 6 3 6 V 5 V 6V 8 V 10 V Pic 6 Power for external device DIP switch ...
Page 53: ...54 Pic 48 Routing configuration example ...
Page 54: ...55 Pic 49 Routing screenshots ...
Page 59: ...60 2 Set COM port number UART port must be configured and assigned to COM client on ...
Page 66: ...67 Pic 61 Setting up RAY 1 as External module by example ...
Page 75: ...76 Pic 71 Records in archives section Archives Configutation ...