39
10
1
10
30
50
70 90 110
20 40 60 80 100 120
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance in k
Ω
1. Temperature limiter:
Check the temperature limiter, if the
burner control unit cannot be reset
after a fault shutdown, although the
boiler water temperature is below
approx. 90 °C.
■ Pull the leads from the sensor.
■ Check the continuity of the temper-
ature limiter with a multimeter.
■ Remove the faulty temperature lim-
iter.
■ Install a new temperature limiter.
■
1
2
3
4
5
6
To reset, briefly turn rotary selector
"
tr
" clockwise as far as it will go
and then back again. The ignition
process will then be repeated.
2. Boiler water temperature sensor:
■ Pull the leads from the sensor.
■ Check the sensor resistance and
compare it with the curve.
■ Replace the sensor in the case of
severe deviation.
!
Please note
The boiler water tempera-
ture sensor is immersed in
the heating water (risk of
scalding).
Drain the boiler before
replacing the sensor.
3. Outlet temperature sensor (gas
combi boiler):
■ Pull the leads from the sensor.
■ Check the sensor resistance and
compare it with the curve.
■ Replace the sensor in the case of
severe deviation.
Danger
The outlet temperature sen-
sor is immersed in the DHW
(risk of scalding).
Drain the DHW side of the
boiler before replacing the
sensor.
Troubleshooting
Repairs
(cont.)
5441 514 UAE
Service