Supply pressure (flow pressure)
Action
For natural gas H
For LPG P
Below 17 mbar
Below 25 mbar
Do not start the boiler. Notify your gas
supply utility or LPG supplier.
17 to 25 mbar
25 to 45 mbar
Start the boiler.
Above 25 mbar
Above 45 mbar
Install a separate gas pressure governor
upstream of the system and regulate the
pre-charge pressure to 20 mbar for natu-
ral gas or 37 mbar for LPG. Notify your
gas supply utility or LPG supplier.
Checking the nozzle pressure
Note
When operating with natural gas E+, the
factory settings must not be altered.
Only check the nozzle pressure at the
lower and upper rated heating output
(with cap
B
on).
The values given in the following tables
are control values for adjusting the max.
heating output (see page 20).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)