32
Display
Measure
Control unit issues
a heat demand
No
Increase set value
and ensure heat is
drawn off
Yes
Ignition
No
Fault
"F4"
Check the ignition
module connec-
tion
Yes
Gas train opens
No
Fault
"F4"
Check the gas
train (control volt-
age 230 V); check
the gas supply
pressure
Yes
Ionisation current
builds (higher than
2µA)
Symbol
A
No
Fault
"F4"
Check the ionisa-
tion current, check
the electrode ad-
justment and the
gas line for air-
locks.
Yes
Burner in opera-
tion
No
Stops below the set
boiler water tem-
perature and re-
starts immediately
Check the flue sys-
tem for tightness
(flue gas recircula-
tion), check the
gas flow pressure
Troubleshooting
Function sequence and possible faults
5441 514 UAE