33
2
f
Faults are indicated by a flashing fault
code (e.g.
"F2"
) and the fault symbol
U
on the display.
Displayed
fault code
System characteris-
tics
Cause
Measures
0A
Burner blocked
Gas supply pres-
sure too low
Check the gas pressure
and the gas pressure
switch.
0C
Burner blocked
Mains voltage too
low
Check the power supply.
0E
Burner blocked
Flue gas monitor
has responded
Check the flue.
Note
If the flue gas monitor re-
sponds 10 times within a
24 h period, the burner en-
ters a fault state (fault
"F6" is displayed).
F2
Burner in a fault
state
The temperature
limiter has respon-
ded
Check heating system fill
level. Check circulation
pump. Vent the system.
Check the temperature
limiter (see page 38)
and connecting cables.
To reset, briefly turn rotary
selector "
tr
" clockwise
as far as it will go and then
back again (reset).
F3
Burner in a fault
state
Flame signal is al-
ready present at
burner start
Check ionisation elec-
trode and connecting ca-
ble.
Switch ON/OFF switch
8
OFF and ON again (or
reset, see F2).
Troubleshooting
Fault messages on the display
5441 514 UAE
Service