67
Fault code
on the dis-
play
System characteris-
tics
Cause
Measures
dE
Control mode without
room influence
Lead break, room
temperature sen-
sor, heating circuit
with mixer M2
Check the room tempera-
ture sensor, heating cir-
cuit with mixer M2 and the
remote control DIP switch
settings (see page 88).
E4
Burner blocked
Supply voltage
fault
Replace the control unit.
E5
Burner in a fault
state
Internal fault
Press "
E
".
Replace the control unit if
the burner will not restart.
E6
Burner in a fault
state
The oil preheater
does not respond
inside the tolerated
time
Check oil pre-heater and
supply line and replace if
necessary.
Press "
E
".
F0
Burner blocked
Internal fault
Replace the control unit.
F1
Burner in a fault
state
Flue gas tempera-
ture limiter has
responded
Check the heating system
fill level. Vent the system.
Press reset button "
E
"
after the flue gas system
has cooled down.
F2
Burner in a fault
state
The temperature
limiter has respon-
ded
Check the heating system
fill level. Check the circu-
lation pump. Vent the sys-
tem. Check the tempera-
ture limiter and connect-
ing cables.
Press "
E
".
F3
Burner in a fault
state
Flame signal is
already present at
burner start
Check ignition electrodes,
electrode gaps and con-
necting cables.
Press "
E
".
Troubleshooting
Fault codes
(cont.)
5692 799 GB