65
Fault code
on the dis-
play
System characteris-
tics
Cause
Measures
b1
Control mode as per
delivered condition
Communication
fault, programming
unit (internal)
Check connections and
replace the programming
unit if required.
b4
Controls as if the out-
side temperature
were 0 °C
Internal fault
Replace the control unit.
b5
Control mode as per
delivered condition
Internal fault
Replace the control unit.
b7
Burner blocked
Boiler coding card
missing, faulty or
incorrect boiler
coding card
Plug in boiler coding card
or replace it, if faulty.
b8
Burner blocked
Lead break, flue
gas temperature
sensor
Check the flue gas tem-
perature sensor (see
page 72).
bA
Mixer M2 regulates to
20 °C flow tempera-
ture
Communication
fault, extension kit
for heating circuit
with mixer M2
Check extension kit con-
nections and code. Start
the extension kit.
bC
Control mode without
remote control
Communication
fault, Vitotrol
remote control,
heating circuit A1
Check connections,
cable, coding address
"A0" and the remote con-
trol DIP switches.
bd
Control mode without
remote control
Communication
fault, Vitotrol
remote control,
heating circuit with
mixer M2
Check connections,
cable, coding address
"A0" and the remote con-
trol DIP switches.
bE
Control mode
Vitotrol remote
control incorrectly
programmed
Check remote control DIP
switch settings (see
page 88).
bF
Control mode
Incorrect LON
communication
module
Replace the LON commu-
nication module.
C2
Control mode
Lead break, KM
BUS to solar con-
trol unit
Check the KM BUS, the
solar control unit and cod-
ing address "54".
Troubleshooting
Fault codes
(cont.)
5692 799 GB