52
Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
C5:20
Electronic minimum flow
temperature limit in
standard mode 20 °C
C5:1
to
C5:127
Minimum temperature limit
adjustable from 1 to 127 °C
(limited by boiler-specific
parameters)
C6:74
Electronic maximum flow
temperature limit 74 °C
C6:0
to
C6:127
Maximum temperature
limit adjustable from 10 to
127 °C (limited by boiler-
specific parameters)
d3:14
Heating curve slope =
1.4
d3:2
to
d3:35
Heating curve slope adjust-
able from 0.2 to 3.5 (see
page 30)
d4:0
Heating curve level = 0
d4:–13
to
d4:40
Heating curve level adjust-
able from –13 to 40 (see
page 30)
d5:0
With external heating pro-
gram changeover: Heat-
ing program switches to
"continuous operation
with reduced room tem-
perature"
d5:1
The external heating pro-
gram changeover changes
the heating program to
"Constant central heating
with standard room tem-
perature"
E1:1
With remote control: Set
day temperature is
adjustable at the remote
control unit from 10 to
30 °C
E1:0
Set day temperature
adjustable from 3 to 23 °C
E1:2
Set day temperature
adjustable from 17 to
37 °C
E2:50
With remote control: No
display correction of the
actual room temperature
E2:0
to
E2:49
Display correction –5 K
or
Display correction –0.1 K
E2:51
to
E2:99
Display corr0.1 K
or
Display corr4.9 K
E5:0
Without variable speed
circulation pump
E5:1
With variable speed circu-
lation pump; automatic rec-
ognition
E6:65
Maximum speed of the
variable speed pump
65 % of max. speed in
standard mode
E6:0
to
E6:100
Maximum speed adjusta-
ble from 0 to 100 % of max.
speed
Codes
Code 2
(cont.)
5692 799 GB