Coding in
the as
delivered
condition
Address:
value
Function mode
Coding
change
Address:
value
Possible change
b0:0
*
1
With remote control:
Heating mode/reduced
mode: Weather-com-
pensated
*
2
b0:1
Heating mode: Weather-
compensated
Reduced mode: With
room temperature hook-
up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tem-
perature hook-up
b2:8
With remote control unit
and for the heating cir-
cuit, heating with room
temperature hook-up
must be encoded:
Room influence factor
8
*
2
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
*
1
With remote control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
tion
*
2
b5:1
to
b5:8
Heating circuit pump
logic function - see the
following table
Parameter
address b5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
1:
active RT
Actual
> RT
Set
+ 5 K; passive RT
Actual
< RT
Set
+ 4 K
2:
active RT
Actual
> RT
Set
+ 4 K; passive RT
Actual
< RT
Set
+ 3 K
3:
active RT
Actual
> RT
Set
+ 3 K; passive RT
Actual
< RT
Set
+ 2 K
4:
active RT
Actual
> RT
Set
+ 2 K; passive RT
Actual
< RT
Set
+ 1 K
5:
active RT
Actual
> RT
Set
+ 1 K; passive RT
Actual
< RT
Set
6:
active RT
Actual
> RT
Set
; passive RT
Actual
< RT
Set
- 1 K
Code 2
(cont.)
57
Coding
56
92
548
GB
*1
Only for weather-compensated control unit.
*2
Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
Summary of Contents for VITODENS 333
Page 114: ...Parts lists cont 114 Parts lists 5692 548 GB ...
Page 115: ...Parts lists cont 115 Parts lists 5692 548 GB ...
Page 116: ...Parts lists cont 116 Parts lists 5692 548 GB ...
Page 117: ...Parts lists cont 117 Parts lists 5692 548 GB ...
Page 118: ...Parts lists cont 118 Parts lists 5692 548 GB ...
Page 119: ...Parts lists cont 119 Parts lists 5692 548 GB ...
Page 131: ...131 5692 548 GB ...