1.
Connect a flue gas analyser at the
flue gas aperture
A
on the boiler
adaptor.
2.
Open the gas shut-off valve, com-
mission the boiler and create a heat
demand.
3.
Select the lower rated output.
Constant temperature control unit:
&
Press both keys
9
and
d
simul-
taneously until the display shows
1.
Weather-compensated control unit:
&
Press both keys
9
and
d
simul-
taneously until the display shows
Relay test.
&
With
a
/
b
in the display, select
Basic load.
4.
Check the CO
2
content. Should the
actual value deviate by more than
1 % from the above range, imple-
ment steps from page 15 (possibly
replace the burner).
5.
Enter actual values into the service
report.
6.
Set the upper rated output.
Constant temperature control unit:
&
With
a
/
b
in the display, select
2.
Weather-compensated control unit:
&
With
a
/
b
in the display, select
Full load.
Further details regarding the individual steps
(cont.)
16
Initial start-up, inspection, maintenance